Electrical installation
Wiring

Operation with another supplier

4.4.2
Operation with another supplier
(
Stop!
ƒ
ƒ
Fig.9−3
Level/time diagrams for operation with other supplier
ECSxü
U
ECSxK
K1
58
After mains connection, wait at least one second before bridging
the charging current limitation (X26 = HIGH).
Only release the controller (X6/SI1 = HIGH) if the charging current
limitation is bridged.
HIGH (1)
ü
ECSx : X6/SI1
LOW (0)
U
ZK
HIGH (1)
ECSxK: X26 (24 V DC)
LOW (0)
HIGH (1)
K1
LOW (0)
Axis module of series ECS
DC−bus voltage
ZK
Capacitor module of series ECS
Mains contactor
l
100 %
0 %
t [s]
t [s]
t [s]
t [s]
1
ECSXK011
EDKCSCK002 DE/EN/FR 1.1