IST-2220.EC04.01/C
TS220EC-H model is as previous, but it uses a sensor suitable for industry and polluted environments and with
presence of other toxic gases.
TS220ES has a sensor that can detect Sulphur dioxide (SO
gas which is a toxic, colourless, with pungent odour, heavier than air (its density as to air is 2.25). His TWA (Time-
Weighted Average) is 2 ppm and STEL (Short Term Exposure Limit) is 5 ppm.
SO
is a strong irritant to eyes and respiratory system. Inhalation may cause pulmonary edema and prolonged ex-
2
posure can lead to death and when it combines with water forms H
TS220EH has a sensor that can detect Hydrogen sulphide (H
toxic, flammable, colorless, with a characteristic odor of rotten eggs, heavier than air (its density as to air is 1.19). His
TWA is 5ppm (Time-Weighted Average) and STEL is 10 ppm (Short Term Exposure Limit). His LEL (Lower Explosive Limit) is
4% volume. The H
S smell is perceived at concentrations above 0.2 ppm, to low levels (50÷100 ppm) already pro-
2
duces irritation to the eyes and throat, cough, fast breathing and training of fluid in the respiratory tract. This gas,
over 150 ppm, acts on the olfactory nerve, making it impossible for the perception of its odour, and higher concen-
trations can cause unconsciousness within a few minutes and can lead to death.
TS220EHCN has a sensor that can detect Hydrogen cyanide (HCN) (synonymous with Hydrocyanic acid, Prussic acid)
gas which is a toxic, extremely poisonous gas, colourless, with has an almond-like odour, a little lighter than air
(its density as to air is 0.94). His TWA (Time-Weighted Average) is 4.7 ppm and STEL (Short Term Exposure Limit) is 10 ppm.
The HCN is a strong irritant to eyes and respiratory system. Inhalation may cause effects on the cellular respira-
tion, resulting in convulsions and unconsciousness. Exposure to 300ppm for 2 minutes may result in death.
TS220EN has a sensor that can detect Nitric oxide (NO) gas which is a toxic and colourless, heavy as air (its den-
sity as to air is 1.04). His TWA (Time-Weighted Average) and STEL (Short Term Exposure Limit) are 25 ppm. NO is a strong
oxidant and reacts with combustible and reducing materials. On contact with the air turns it into nitrogen dioxide
(NO
). Nitric oxide is irritating to eyes and respiratory tract. Inhalation can cause pulmonary edema, may also have
2
effects on the blood, causing the formation of metaemoglobina. In more severe cases it can lead to death. Nitric ox-
ide is a pollutant that is generated in part in combustion processes, in part by emissions from natural volcanic erup-
tions, fires or civil activities and industrial processes involving combustion, such as transport (vehicles with diesel en-
gine, gasoline, LPG, etc.) and the production of heat and electricity.
TS220EN2 has a sensor that can detect Nitrogen dioxide (NO
characteristic sharp, biting odour, heavier than air (its density has to air is 1.58). His TWA (Time-Weighted Average) is 3
ppm and STEL (Short Term Exposure Limit) is 5 ppm. NO
NO
is formed in most combustion processes using air as the oxidant. At elevated temperatures nitrogen combines
2
with oxygen to form nitrogen dioxide. The most important sources of NO
plants, heating and vehicles, especially diesel engines). NO
lungs, pulmonary edema and death as it is capable of combining with the haemoglobin by changing the chemical
and physiological, forming metaemoglobina which is no longer able to carry oxygen to the tissues. Also, low con-
centrations (4 ppm) will anesthetize the nose.
TS220EHCl has a sensor that can detect Hydrogen cloride (HCl) (synonymous with Hydrogen chloride, muriatic acid)
which is normally a liquid, which releases a toxic gas, colorless with a pungent odor, heavier than air (its density has
to air is 1.3). His TWA (Time-Weighted Average) is 5 ppm and STEL (Short Term Exposure Limit) is 10 ppm.
This gas, In aqueous solution becomes one of the most corrosive liquids. The vapors are corrosive to eyes, the
skin and the respiratory tract. Inhalation of high gas concentrations may cause pneumonitis and pulmonary edema.
OPERATIONAL DESCRIPTION
The electrochemical sensor is temperature compensated, but is sensitive to extreme humidity variations. The cali-
bration is carried out with specific gas to be detected. Anyway, it can contemporaneously detect other gases that
should be present in the same environment as listed in
Preheating: when powered, the sensor needs a time of preliminary heating of about 60 seconds. During this pe-
riod the yellow Led "FAULT" flashes. After this period, the yellow Led light off, the green Led "ON" illuminates to indi-
cate normal functioning. After this period the unit is able to detect gas even if it attains the optimum stability condi-
tions after about 4 hours continual functioning.
Normal operation: the green Led "ON" should be light on.
Alarm: The red Led (ALARM) illuminates (only if it be activate by Dip-Switch no.1 set to ON) if the gas concentration ex-
ceeds the value indicated in the table below, depending on the model.
TS220EA
TS220EC-S
TS220EA-H
TS220EC-H
50 ppm NH
200 ppm CO
3
Faults: the yellow Led illuminates and the "S" output falls down to 0mA. (The different faults are listed below).
Yellow Led illuminates each 4 seconds (with green Led activate): this happens when the "Cartridge Sensor" has
overcome its theoretical period of life and its correct operation is not longer guaranteed. The detector keeps on op-
erating normally but it is necessary to replace, as soon as possible, the "Cartridge" with a new one. The type to be
required is described on
Yellow Led activate, green Led off (0 mA output signal): this signal different kind of faults. 1) The Dip-Switch set
up is wrong, please verify
"Cartridge" is installed or it is not correctly connected or a not compatible one is mounted. Please check the car-
tridge connections and compatibility
condition does not change, it will be necessary to replace the unit and/or send it back to the supplier to repair.
TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI )
Istruzione / User's Manual / Manuel d'utilisation
TS220ES
TS220EH
10 ppm SO
20 ppm H
2
Page
1. The replacement procedure is described in the attached manual.
(see Table
4). 2) The "Cartridge" is not working, please replace with new one. 3) If a new
(see on page
) (also Sulphurous anhydride, Sulphurous oxide, Sulphur oxide)
2
S (Hydrogen sulphide).
2
S) (synonymous with hydrogen sulphide) gas which is a
2
) gas which is a reddish-brown toxic gas with a
2
combined with water turns into nitric acid and nitric oxide.
2
is toxic by inhalation, it can cause irreversible damage to the
2
tables 2 and
3.
TS220EHCN
S
5 ppm HCN
2
1) these checks are made switching off and on the device. If the
are internal combustion engines (power
2
TS220EN
TS220EN2
25 ppm NO
30 ppm NO
2
Tel: 02/26 92 28 90 Fax: 02/21 33 734
Pag.8/16
TS220EHCl
5 ppm HCl