Setting Of The Air Damper Actuator; Combustion Check - Riello Burners GS20D Manuel D'entretien

Brûleur gaz à air soufflé
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.3 SETTING OF THE AIR DAMPER ACTUATOR

PAUSE
I CAM
The I cam is factory set to allow the air damper to fully
close on shutdown. (Reference value 0°).
Do not modify this setting for any reason.
FIRST STAGE
V CAM
The V cam controls the air for the 1
The cam must be adjusted on decrease (damper closing)
by adjusting the micrometer screw.
The definitive position is obtained after 2
ment.
SECOND STAGE
II CAM
The II cam controls the air for the 2
(Reference value 60°, not to exceed 70°).
Do not modify this setting for any reason.
The regulation of airflow at 2
air damper (1, fig. 2).
The III cam controls the opening of the gas valve at 2
must precede the II cam by at least 15°.
Warning:
For power adjustment at 1
tions:
– the power ratio between 1
mum, if the above ratio is exceeded, valve seal control must be
used;
– in any case, the minimum burner power at 1
less than the firing rate range.

4.4 COMBUSTION CHECK

It is advisable to set the burner according to the type of gas used and following the indications of the table:
EN 676
Theoretical max. CO
GAS
0 % O
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
IONIZATION CURRENT
The minimum current necessary for the control
box operation is 3 μA.
The burner normally supplies a higher current
value, so that no check is needed. However, if
you want to measure the ionization current, you
must open the connector fitted to the red wire
and insert a microammeter.
20033980
st
stage flame (2, fig. 2).
nd
stage adjust-
nd
stage flame.
nd
stage is carried out by operating the
st
nd
and 2
stage, apply the following indica-
st
nd
and 2
stage must be 1 : 2 at a maxi-
st
Setting CO
2
 = 1.2
2
9.7
9.5
11.6
11.4
Micrometric screws
D1777
nd
stage and
stage must not be
AIR EXCESS:
max. output   1.2 – min. output   1.3
%
2
 = 1.3
9.0
8.8
10.7
10.5
Terminal board
of control-box
10
7
GB
Fig. 2
E9085
CO
mg/kWh
mg/kWh
100
100
100
100
Connector
D5006
2
1
NO
x
170
170
230
230
Probe

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

577t1

Table des Matières