ELECTRICAL CONNECTIONS

As standard, these units are equipped with a local switch acting as a mains supply terminal block.
This switch can be padlocked.
A trip switch or a fuse holder (not supplied) must be installed upstream of the unit, in accordance with the wiring
diagram.Refer to the electrical specifications for the fuse ratings .
MODELS
205 - 305 - 405M
press to unclip and remove the local
switch from the electrical board.
3N~400V-
Use a pOZIDRIV M 3.5, Z screwdriver for connecting the wires.
3N~400V-
Use a key for hexagonal socket screws of 4mm for connecting the wires.

VERY IMPORTANT:

The outdoor unit is equipped as standard with a phase sequence and cut-out controller located in the electrical box.
ThIS PRODUCT IS EQUIPPED WITh A PhASE SEQUENCE CONTROLLER. ThE LED's INDICATE ThE
Green LED = 1
Yellow LED =1
Low voltage supply
T h e c o m p r e s s o r r o t a t i o n
direction is correct
Green LED = 1
405 - 505 - 605 - 755
Maximum tightening torque
models 205 - 305 - 405M
models 405 - 505 - 605 - 755
Couple de serrage maxi
Modèle 905
3N~400V-50hZ+
FOLLOWING CONDITIONS:
Yellow LED =0
phase inversion or phase absent
(L1)
The compressor and the fans
do not start.
Green LED = 0
14
MODELS
2,1Nm
4Nm
6Nm
Yellow LED =0
phase absent (L2 or L3)
the compressor and the fans do
not start.