Technical Specifications - LEGRAND WHAD 3 100 96 Manuel D'installation

Onduleurs
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1

9 Technical specifications

Construction specifications
Weight
Size L x H x P in mm
Technology
Computer interface
Protection features
Internal, synchronised bypass
environmental specifications
Maximum altitude for storage
Storage temperature range
Operating temperature range
Range of relative humidity for operation
Grade of protection according to IEC529
Noise level at 1 metre
nominal input voltage
Nominal input voltage
Range of input voltage (nominal load)
Range of input voltage (50% nominal load)
Nominal input frequency
(selectable by the operator)
Whad 2, 2.5 kVA
3 100 96
3 101 09
3 101 10
25 Kg
160 x 460 x 420
PWM high frequency both for input stage
and output stage.
Microprocessor control logic.
Standard serial RS232 for interfacing with
personal computer using the diagnostic
software supplied, output to 9 pin, female,
SELV insulated, DB9 connector
Electronic protection against overloads, short
circuits and excessive battery discharge.
Operation block at end of autonomy.
Inrush current limitation when switching on.
Sensor for correct neutral connection
Back feed protection (electrical insulation
for the safety of the input plug during
operation in battery mode)
Automatic. Intervenes in case of overload
and operation anomaly
1000 metres
from -20°C to +50°C
from 0°C to 40° C
From 20% to 80% non condensing
IP21
42 dBA
230 V
From 184V to 264V
From 110V to 264V
50Hz/60HZ +/- 2%
3 100 97
3 101 11
3 101 12
27