9 Technical features
CONSTRUCTION SPECIFICATIONS
Weights
Dimensions L x H x P in mm
Protection
Ambient specifications
Operating temperature range
Operating relative humidity range
Degree of protection as per IEC529
Noise level at 1 meter
Electrical input specifications
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Number of input phases
Waveform on output
With battery operation
Type of operation
Electrical specifications on output
Rated output voltage
Output current on nominal load
Apparent output capacity on nominal load
Apparent output capacity on nominal load
Overload capacity
Number of phases on output
3 100 02
3 100 09
3 100 22
7 Kg.
95 X 171 X 349
Electronic protection against overloading
and short-circuiting. Shutdown on
reaching operating limit and overheating.
Automatic shutdown due to protection
triggering
from 0 to +40 °C
from 0 to 95% non-condensing
IP20
< 40 dBA
230 V
from 160 V to 290 V
50-60 Hz +/-5Hz
3,75 Arms
Single phase
step wave
line interactive
230 V ± 10 %
2,6 Arms
300 W
600 VA
110% for 5 s.
Single phase
Niky 600/800
3 100 03
3 100 10
3 100 23
7,5 Kg.
5 Arms
3,48 Arms
400 W
800 VA
19