CONTROLS IN CASE OF OPERATION PROBLEMS
Blink code
2 blinks
• •
3 blinks
• • •
4 blinks
• • • •
5 blinks
• • • • •
6 blinks
• • • • • •
7 blinks
• • • • • • •
8 blinks
• • • • • • • •
9 blinks
• • • • • • • • • • • • • • •
10 blinks
• • • • • • • • • • • • • • • •
Operational status indication
Status
Oil pre-heater heats, waiting time <<tw>>
Ignition phase, ignition controlled
Operation, flame O.k.
Operation, flame not O.k.
Undervoltage
Fault, alarm
Output of fault code (refer to <<Fault code table>>)
Extraneous light prior to burner start-up
Interface diagnosis
Legend:
Off
Yellow
Error code table
Possible cause
No establishment of flame at the end of <<TSA>>
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition
Free
Extraneous light on burner start-up
Free
Free
Too many losses of flame during operation
(limitation of the number of repetitions)
- Faulty or soiled fuel valves
- Faulty or soiled flame detector
- Poor adjustment of burner
Time supervision oil pre-heater
Free
Wiring error or internal error, output contacts
Colour code table
Green
Red
23 / 56 0006080843
Colour code
Red flicker light
E
N
G
L
I
S
H
Colour
Yellow
Yellow-off
Green
Green-off
Yellow-red
Red
Red-off
Green-red