Select Fan Relay Setting For No2 - "Frs.n; Select Fan Relay Delay Setting - "Frd; Select Fan Relay Minimum Runtime Setting - "Frr - Macurco CX-6 Manuel D'instructions

Détecteur, régulateur et transducteur combiné de monoxyde de carbone et de dioxyde d'azote
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Macurco CX-xx Manual (Rev-1.0) Eng
3. Push Next 7 times to get to "FrS.C" or Fan Relay Setting for CO.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.10 Select Fan Relay Setting for NO2 – "FrS.n"
Available options are "diS", 0.5, 0.7, 1.0, 1.2, 1.5, 1.7, 2.0, 2.2, 2.5 (default), 2.7, 3.0, 3.2, 3.5, 3.7, 4.0, 4.2, 4.5, 4.7,
5.0.
To select the Fan Relay Setting for NO2, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 8 times to get to "FrS.n" or Fan Relay Setting for NO2.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.11 Select Fan Relay Delay Setting – "Frd"
Available options are 0, 1, 3 (default), 5, 10.
To select the Fan Relay Delay Setting, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 9 times to get to "Frd" or Fan Relay Delay Setting.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.12 Select Fan Relay Minimum Runtime Setting – "Frr"
Available options are 0 (default), 3, 5, 10, 15.
To select the Fan Relay Minimum Runtime Setting, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 10 times to get to "Frr" or Fan Relay Minimum Runtime Setting.
REV – 1.1