Macurco CX-xx Manual (Rev-1.0) Eng
To select the Power Up Test Configuration, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 1 time to get to "PUt" or Power Up Test Configuration.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.4 Select Display Configuration – "dSP"
Available options are "On" (default), "OFF".
To select the Display Configuration, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 2 times to get to "dSP" or Display Configuration.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.5 Select Buzzer Configuration – "bUZ"
Available options are "On" (default), "OFF".
To select the Buzzer Configuration, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 3 times to get to "bUZ" or Buzzer setting.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.6 Select Alarm Relay Setting for CO – "ArS.C"
Available options are "diS", 50, 100, 150, 200 (default).
To select the Alarm Relay Setting for CO, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.