Select Alarm Relay Setting For No2 - "Ars.n; Select Alarm Relay Configuration - "Arc; Select Fan Relay Setting For Co - "Frs.c - Macurco CX-6 Manuel D'instructions

Détecteur, régulateur et transducteur combiné de monoxyde de carbone et de dioxyde d'azote
Masquer les pouces Voir aussi pour CX-6:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Macurco CX-xx Manual (Rev-1.0) Eng
2. Push the Enter button to enter the Con menu.
3. Push Next 4 times to get to "ArS.C" or Alarm Relay Setting for CO.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.7 Select Alarm Relay Setting for NO2 – "ArS.n"
Available options are "diS", 1.0, 2.0, 3.0, 4.0, 5.0 (default), 6.0, 7.0, 8.0, 9.0, 10.0, 11.0, 12.0, 13.0, 14.0, 15.0, 16.0,
17.0, 180.0, 19.0, 20.0.
To select the Alarm Relay Setting for NO
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 5 times to get to "ArS.C" or Alarm Relay Setting for NO
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.8 Select Alarm Relay Configuration – "Arc"
Available options are "nO" (default), "nC".
To select the Alarm Relay Configuration, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
3. Push Next 6 times to get to "Arc" or Alarm Relay Configuration.
4. Push Enter. The display will show the current setting.
5. Push Next to cycle through the available settings (display will begin flashing).
6. Push Enter to confirm the new setting (display will stop flashing).
7. Push Enter once more to return to the configuration menu.
8. Push Next until "End" is displayed.
9. Push Enter to return to normal operation.
4.5.9 Select Fan Relay Setting for CO – "FrS.C"
Available options are "diS", 15, 25, 35 (default), 50, 100.
To select the Fan Relay Setting for CO, in normal mode:
1. Push the Next button to get to "Con" or the Configuration menu.
2. Push the Enter button to enter the Con menu.
REV – 1.1
, in normal mode:
2