NOTE 2: The cable for M5T 15k (SB) HV should be able to withstand over 30A current. It is
recommended to use 6mm²/12 AWG or thicker wire
NOTE 3: The cable for M5T 20k (SB) HV et M5T 10k (SB) LV should be able to withstand over 40A
current. It is recommended to use 10mm²/10 AWG or thicker wire
NOTE 4: The cable for M5T 30k TT (S) HV or E4 Evolution II 15k TT (S) LV should be able to
withstand over 60A current. It is recommended to use 16mm²/8 AWG or thicker wire
NOTE 5: The cable for for M5T 40k (SB) HV et M5T 20k (SB) LV should be able to withstand over 80A
current. It is recommended to use 16mm²/6 AWG for safety and efficiency.
NOTE 6: The cable for for M5T 60k (SB) HV et M5T 30k (SB) LV should be able to withstand over
107A current. It is recommended to use 25mm²/4AWG for safety and efficiency.
5)
Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect
the earth wire last when making wire disconnection!)
a) Terminal block wiring diagram for M5T 10/15/20k (WOB) HV (3/3)
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron, France – www.infosec-ups.com
89
Hotline : +33 (0)2 40 76 15 82 – Fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 22 AA 59 203 08
M5T 10k (S) LV (3/3) – Dual input
b) Terminal block wiring diagram for M5T 10/15/20k (WOB) HV (3/3)
M5T 10k (SB WOB LV (3/3) – common input