BATTERY
➢
BATT Warning VOL:
◼
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is
default setting.
◼
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is
default setting. This parameter setting is related to "Shutdown Voltage" setting. This
setting value should be higher than "Shutdown Voltage" setting.
➢
Shutdown VOL: If battery voltage is lower than this point in battery mode, UPS will
automatically shut down. The setting range is 10V ~ 12V. 10.7V is default setting. (This
setting is only available for long-run model)
➢
Battery Parameters:
◼
Battery AH: setting battery capacity
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron, France – www.infosec-ups.com
112
Hotline : +33 (0)2 40 76 15 82 – Fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 22 AA 59 203 08
Battery setting page