2-3. Single UPS Installation

Installation and wiring must be performed in accordance with the local electric laws/regulations and the
following instructions executed by qualified personnel.
1)
Make sure the mains wire and breakers in the building are in compliance with the standard of rated
capacity of the UPS to avoid hazard of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less
than the UPS's maximum input current. Otherwise the receptacle may be burned and destroyed.
2)
Switch off the mains switch in the building before installation.
3)
Turn off all the connected devices before connecting to the UPS.
4)
Prepare wires based on the following table (use flexible cables):
HV Model
M5T 10K 3/3
M5T 10K WOB 3/3
M5T 10K 3/1
M5T 10K WOB 3/1
M5T 15K 3/3
M5T 15K WOB 3/3
M5T 15K 3/1
M5T 15K WOB 3/1
M5T 20K 3/3
M5T 20K WOB 3/3
M5T 20K 3/1
M5T 20K WOB 3/1
M5T 30K
M5T 30K WOB
M5T 40K
M5T 40K WOB
M5T 60K S
LV Model
M5T 10K 3/3
M5T 10K WOB 3/3
M5T 10K 3/1
M5T 10K tri/ WOB 3/1
M5T 15K
M5T 15K WOB
M5T 20K
M5T 20K WOB
M5T 30K S
NOTE 1: The cable for M5T 10k (SB) HV should be able to withstand over 20A current. It is recommended
to use 6mm²/14 AWG or thicker wire for Phase
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron, France – www.infosec-ups.com
88
Hotline : +33 (0)2 40 76 15 82 – Fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 22 AA 59 203 08
Input(Ph)
Bypass(Ph)
6 / 14
6 / 14
6 / 14
6 / 14
6 / 8
6 / 14
6 / 8
6 / 14
6 / 12
6 / 12
6 / 12
6 / 12
6 / 12
6 / 6
6 / 12
6 / 6
10 / 10
10 / 10
10 / 10
10 / 10
10 / 10
10 / 4
10 / 10
10 / 4
16 / 8
16 / 8
16 / 8
16 / 8
16 / 6
16 / 6
16 / 6
16 / 6
25 / 4
Input(Ph)
Bypass(Ph)
10 / 10
10 / 10
10 / 10
10 / 10
10 / 10
10 / 4
10 / 10
10 / 4
16 / 8
16 / 8
16 / 8
16 / 8
16 / 6
16 / 6
16 / 6
16 / 6
25 / 4
Wiring spec (mm²/AWG)
Output(Ph)
Neutral
6 / 14
6 / 10
6 / 14
6 / 10
6 / 8
6 / 8
6 / 8
6 / 8
6 / 12
6 / 10
6 / 12
6 / 10
6 / 6
6 / 6
6 / 6
6 / 6
10 / 10
10 / 6
10 / 10
10 / 6
10 / 4
10 / 4
10 / 4
10 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
25 / 4
25 / 4
Wiring spec (mm²/AWG)
Output(Ph)
Neutral
10 / 10
10 / 6
10 / 10
10 / 6
10 / 4
10 / 4
10 / 4
10 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
25 / 4
25 / 4
Battery
Ground
6 / 8
6 / 8
6 / 8
6 / 8
6 / 8
6 / 8
6 / 8
6 / 8
6 / 8
6 / 6
6 / 8
6 / 6
10 / 6
10 / 8
10 / 6
10 / 4
10 / 8
10 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
-
-
Battery
Ground
10 / 6
10 / 6
8
10 / 4
10 / 8
10 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
16 / 4
-
-