M5T LV (208V)
CAPACITY*
INPUT
Low Line Loss
Voltage
Low Line Comeback
Range
High Line Loss
High Line Comeback
Frequency Range
Phase
Power Factor
OUTPUT
Phase
Output voltage
AC Voltage Regulation
Frequency Range
(Synchronized Range)
Frequency Range (Batt. Mode)
AC mode
Overload
Battery mode
Current Crest Ratio
Harmonic Distortion
Line
Transfer
Inverter
Time
Inverter
EFFICIENCY
AC mode
ECO mode
Battery Mode
BATTERY
Type
Numbers
Standard
Recharge Time
Model
Charging Current(max.)
Charging Voltage
Type
Numbers
Long-run
Model
Charging Current(max.)
Charging Voltage
PHYSICAL
Dimension, D X W X H
Standard
mm
Model
Net Weight (kgs)
Dimension, D X W X H
Long-run
mm
Model
Net Weight (kgs)***
ENVIRONMENT
Operation Temperature
Operation Humidity
Operation Altitude**
Acoustic Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
SALES INFORMATIONS
Warranty
* If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m.
**Product specifications are subject to change without further notice.
***Weight without batteries
INFOSEC UPS SYSTEM – 15, rue du Moulin – 44880 Sautron, France – www.infosec-ups.com
143
Hotline : +33 (0)2 40 76 15 82 – Fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 02 22 AA 59 203 08
M5T 10K (WOB)
10KVA / 10KW
3 x 208/220 VAC
(3Ph+N) or
120/127 VAC
(Ph+N)
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% :
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% :
≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load (PF≥0.8)
Battery
Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
ECO
12 V / 9 Ah
(8+8)pcs
1.0 A ± 10% (Recommended) 1.0~12.0A (Adjustable)
627 x 250 x 826
125
627 x 250 x 826
45
Less than 60dB @ 1
Meter
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Power management from SNMP manager and web browser
M5T 15K (WOB)
15KVA / 15KW
70 VAC(Ph-N) ± 3 % at 50% Load
88 VAC(Ph-N) ± 3 % at 100% Load
Low Line Loss Voltage + 5V
156 VAC(L-N) ± 3 % at 50% Load
146 VAC(L-N) ± 3 % at 100% Load
High Line Loss Voltage - 5V
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
3 Phase with Neutral
≧ 0.99 at 100% Load
3 Phase with Neutral
3 x 208/220 VAC (3Ph+N)
± 1%
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
immediately
immediately
3:1 max
0 ms
<10 ms
93.5%
98.5%
92.5%
12 V / 7 Ah
(8+8)pcs x 4 strings
9 hours recover to 90% capacity
+/-109 VDC ± 1%
Depending on applications
16 ~ 20 (adjustable)
1.0~12.0A±10% (Adjustable)
+/- 13.65 VDC * N ± 1% (N = 8~10)
815 x 300 x 1000
213
78
0 ~ 40°C (the battery life will down when > 25°C)
<95 % and non-condensing
<1000m**
Less than 65dB @
1 Meter
1 year
M5T 20K (WOB)
M5T 30K S
20KVA / 20KW
30 KVA / 30 KW
12 V / 9 Ah
1~18A (adjustable)
243
815 x 300 x 1000
87***
80
Less than 70dB @ 1 Meter
-
-