15.1 Turn the temperature selector (a) to the hot water stop.
15.2 Use the Allen key to push in the stop.
15.3 Turn the temperature selector (a) in an anti-clockwise direction up to the stop.
15.4 Trigger the fitting.
15.5 Measure the hot water temperature.
15.6 If the hot water temperature is > 70°C, the fitting should be flushed for at least
3 minutes. Trigger the fitting several times for this purpose.
The thermal disinfection process must be recorded (room, tapping point, date, time,
temperature, duration).
15.7 Turn the temperature selector (a) clockwise until it engages.
Caution!
The temperature selector (a) may not be turned beyond the stop in an anti-
clockwise direction.
15.8 Test the limit stop.
15.9 Trigger the fitting to drain the remaining hot water.
15.10 Measure the water temperature. The maximum water temperature may not exceed
40°C (see
Chapter
Once thermal disinfection has been completed, the scald protector does not need to
be reset.

16. Thermal disinfection -automatic-

Caution!
The directions in the Thermal Disinfection Planning Aid (01805618) must be
adhered to.
Required accessories
ECC2 function controller (60 W)
with Ethernet connection . . . . . 2000108123
Bypass solenoid valve cartridge . . 2000100431
17.).
11