P2 parameter group - room unit address
No. Description
ROOM UNIT ADDRESS
This setting determines room unit address. It can
be 1 or 2.
P2.1
During initial operation, room unit address is set
automatically.
S1 parameter group - service parameters
No. Description
ROOM TEMPERATURE
This setting determines which sensor is used for
room temperature.
S1.2
Info:
For setting 3, median value of the installed and
auxiliary sensor is calculated for room temperature.
CALIBRATION OF BUILT-IN TEMPERATURE
SENSOR
S1.3
This setting determines the correction of measured
temperature of the built-in sensor.
AUXILIARY TEMPERATURE SENSOR (AUX)
CALIBRATION
S1.4
This setting determines the correction of measured
temperature of the auxiliary sensor.
RELATIVE HUMIDITY SENSOR CALIBRATION
S1.5
This setting determines the correction of measured
relative humidity in the room.
AIR PRESSURE SENSOR CALIBRATION
S1.6
This setting determines correction of measured air
pressure.
AIR QUALITY SENSOR CALIBRATION
S1.7
This setting determines the correction of measured
air quality.
LIGHT SENSOR CALIBRATION
S1.8
This setting determines the correction of measured
lighting in the room.
LOCKING THE MENU
S1.9
This setting limits access to parameter groups in
the menu.
20 English
Range
0 - auto setting
1 - address 1
2 - address 2
Range
0 - none
1 - built-in sensor
2 - auxiliary sensor (AUX)
3 - built-in and additional
sensor
-5,0 ÷ 5,0 °C (0,0)
-5,0 ÷ 5,0 °C (0,0)
-10 ÷ 10 % (0)
-100 ÷ 100 mb (0)
-1000 ÷ 1000 (0)
0,5÷ 2 (1)
0 - no lock
1 - S1
2 - P1, P2 and S1