nVent RAYCHEM HWAT-ECO-GF Mode D'emploi page 14

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

131°F
Test
program
Reset
SYSTEM
INFO, RESET, SERVICE, TEST....
HEATING CABLE & PIPE
CABLE TYPE, PIPE DAIMETER,...
Service
GENERAL SETTINGS
COUNTRY, LANGUAGES, UNITS,...
Status
WATER TEMP. & PROGRAM
APPARTMENT, MAINTAIN, ECONOMY,....
INFO
TEST PROGRAM
Key lock
RESET
SERVICE
STATUS
HEATING CABLE & PIPE
SELECT CABLE TYPE
SELECT PIPE DIAMETER
SELECT INSULATION THICKNESS
SELECT AMBIENT TEMPERATURE
SELECT BOILER SENSOR
SELECT BOILER CUT-OFF TEMPS.
Selection of
parameters
HWAT cable
Pipe
diameter
Insulation
thickness
Boiler sensor
Boiler low
temperature
limit
Boiler high
temperature
limit
14 | nVent.com
The test program runs for 30 minutes, during which all
parameters will be ignored to check the heating cable and
the connection on site. You can stop the test program at
any time.
SETTING
Select "Yes" to activate the Quick install menu and return
all settings to factory settings.
Quick start process restarts automatically.
Access for nVent SERVICE TEAM
Info on current status of the control unit:
Pipe temperature
Boiler temperature
Maintain temperature
Supply voltage
SYSTEM
Duty cycle
Power output
Max power output
Load current
When key lock is "On", the setup and timer menus are
protected by password. To unlock the unit, enter the
predefined password (3000). The unit will automatically
lock itself after 10 mins of inactivity or when Lock "on" key
is pressed. To deactivate the Key lock, press "OFF".
HEATING CABLE & PIPE
HWAT-R2
DN 25
40 MM
20 °C
ON
35/85 °C
Every parameter line shows the actual value /attribute for
each parameter.
Select the type of cable used in your installation
(HWAT-R2).
Set the pipe diameter. You can change the value from 1/2"
(DN 15) up to 4" (DN 100)
Set the insulation thickness. You can change the value from
0,35" to 5,30" ( 9mm to 130 mm) with the pipe diameter as
the limiting value.
Activate/deactivate a connected boiler sensor by clicking
on ON/OFF. The external temperature sensor measures the
boiler temperature. The trace boiler setting is included to
ensure that the heating cable temperature does not exceed
the boiler temperature. The HWAT-ECO-GF memorizes the
highest measured temperature over the last 24 hours.
If the boiler temperature is too low, the maximum
temperature is lowered to the boiler temperature minus the
trace temperature. In this case the green trace boiler LED
will be on.
You can determine the low temperature limit. If the boiler
temperature reaches this value, the unit will switch off the
heating system in order to fulfil hygienic requirements and
avoid energy waste.
You can determine the high temperature limit.
If this value is reached the unit will switch off
the heating system to avoid scalding.
131°F
ECONOMY TEMP
AT 05:00 p.m.
BOILER
140 °F
14 : 17
14 : 17
14 : 17
SELECT COUNTRY
SELECT DATE
SELECT TIME
SELECT ALARM
SELECT SAVING TIME
SELECT WATER TEMPERATURE
SELECT PROGRAM
PROGRAM TIMER
WAT

Publicité

Table des Matières
loading

Table des Matières