Troubleshooting; Technical Support Options; What's Special About Www.dartcontrols.com - DART Controls MPD CONTROL Serie Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Problem
Possible Case
Display is blank
Power not applied
Defective unit
Display is dim
Display intensity
parameter is too low
When power is
AC line supplying
applied, "LF-L" is
power to unit has too
displayed
much noise
AC line supplying
power to unit has an
abnormally low
frequency
When power is
AC line supplying
applied, "LF-H" is
power to unit has too
displayed
much noise
AC line supplying
power to unit has an
abnormally high
frequency
The alarm output
Alarm output
does not seem to
parameters not
function
configured properly

Technical Support Options

Visit the Dart Controls Web Site at: www.dartcontrols.com
Email technical support at: techsupport@dartcontrols.com
Telephone technical support at 317-733-2133 ext. 4

What's Special About www.dartcontrols.com?

Changes to printed material and product offerings fi rst appear online
Product manuals and other literature are easily accessible
All information can be easily displayed or printed as needed

Troubleshooting

Using a volt meter, verify that a voltage between 85 and 265VAC is measured between
the L and N terminal block positions.
Contact technical support for additional help and instructions.
Editing and increasing the display intensity parameter should cause the display digits to
become brighter.
Review routing of power wires in machine to minimize electrical noise. Look for other
devices which share the same circuit which may be producing unacceptable levels of
line noise. In some applications, such as welding equipment, a careful regiment of
applying an AC line filter, re-routine wires, dividing circuits, using shielded cable, and
properly grounding devices will usually solve the problem.
The unit is designed to operate with AC lines from 48-62 Hertz (cycles per second).
This is typically not a problem because the international standards are 50 and 60 Hertz.
Review routing of power wires in machine to minimize electrical noise. Look for other
devices which share the same circuit which may be producing unacceptable levels of
line noise. In some applications, such as welding equipment, a careful regiment of
applying an AC line filter, re-routine wires, dividing circuits, using shielded cable, and
properly grounding devices will usually solve the problem.
The unit is designed to operate with AC lines from 48-62 Hertz (cycles per second).
This is typically not a problem because the international standards are 50 and 60 Hertz.
Alarm output parameters not configured properly
Review alarm output parameters. The alarm relay output can be tested by selecting
the "Always On" value for the Activation Condition parameters for the alarm output.
When doing this, the relay click should be audible and the NC (Normally Closed) and C
(Common) terminals should become internally shorted at the terminal block.
24
Solution