6 Technical Data
6 Technical Data
Repeater
Ord. code
Voltage/power supply
Operating voltage
Current input for +24 V
for +48 V
Power consumption for +24 V
for +48 V
Signaling contact
Maximum switch voltage
Maximum switch current
Signal transmission
Transmission rate
Cascadability
Signal processing time
(any input/output)
Electrical port
Input/output signal
PIN assignment of Port 1
Length of Modbus Plus cable
Connection capability
Electrical isolation
– Shielding/housing
– Data lines/shielding
Optical interface
Typ. wavelength
Launchable optical power
– into fiber E 10/125
– into fiber G 50/125
– into fiber G 62.5/125
– into fiber S 200/230 (HCS
Receiver sensitivity
Transmission distance with 2 dB
system reserve / line attenuation
– with fiber E 10/125 (0.5 dB/km)
– with fiber G 50/125 (1.0 dB/km)
– with fiber G 62,5/125 (1.0 dB/km)
– with fiber G 50/125 (3.0 dB/km)
– with fiber G 62.5/125 (3.5 dB/km)
– with fiber S 200/230 (HCS
Optical connector
* Because of the the ring redundancy's specific requirements, the distance between two OZD Modbus Plus G12-
1300 must not exceed 8 km .
Version 04 07/2014
OZD Modbus Plus G12
943 740-021
+24 VDC –20 % ... +48 VDV +10 %, non-interchangeable,
electrically isolated from the housing, safety extra-low voltage
150 mA
85 mA
3.6 W
4.0 W
30 VDC; 42 VAC (safety extra-low voltage)
1.0 A
1 MBit/s
As required
<1 µs
Modbus Plus level
See Section 3.4
100 m
Max. 31 terminal data devices
No
Yes
860 nm
–15 dBm
–14 dBm
®
)
–10 dBm
–25 dBm
1)
2)
or 3 dB
–
–
–
0 - 2.3 km/10 dB
0 - 2.3 km/11 dB
®
) (8.0 dB/km)
0 - 1.5 km/15 dB
BFOC/2.5 (ST
(resistive load)
®
)
OZD Modbus Plus G12-1300
943 821-021
1310 nm
–19 dBm
–17 dBm
–17 dBm
–
–27 dBm
1)
0 - 8 km */8 dB
2)
0 - 7 km/10 dB
2)
0 - 7 km/10 dB
–
–
–
45