Allen-Bradley PowerFlex FRN 6 Serie Guide De Mise En Route page 11

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 27
See the PowerFlex 4 User Manual for more information on parameters.
Display Group Parameters
No.
Parameter
d001 [Output Freq]
d002 [Commanded Freq]
d003 [Output Current]
d004 [Output Voltage]
d005 [DC Bus Voltage]
d006 [Drive Status]
d007-
[Fault x Code]
d009
d010 [Process Display]
d012 [Control Source]
d013 [Contrl In Status]
d014 [Dig In Status]
d015 [Comm Status]
d016 [Control SW Ver]
d017 [Drive Type]
d018 [Elapsed Run Time]
d019 [Testpoint Data]
d020 [Analog In 0-10V]
d021 [Analog In 4-20mA]
d024 [Drive Temp]
Smart Start-Up with Basic Program Group Parameters
= Stop drive before changing this parameter.
No.
Parameter
P031 [Motor NP Volts]
Set to the motor nameplate rated volts.
P032 [Motor NP Hertz]
Set to the motor nameplate rated frequency.
P033 [Motor OL Current]
Set to the maximum allowable motor current.
P034 [Minimum Freq]
Sets the lowest frequency the drive will output continuously.
P035 [Maximum Freq]
Sets the highest frequency the drive will output.
P036 [Start Source]
Sets the control scheme used to start the drive.
(1)
When active, the Reverse key is also active unless disabled by A095 [Reverse Disable].
P037 [Stop Mode]
Active stop mode for all stop sources [e.g. keypad,
run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set for "3-Wire" control.
When in three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode].
(1)
Stop input also clears active fault.
P038 [Speed Reference]
Sets the source of the speed reference to the
drive.
Important: When A051 or A052 [Digital Inx Sel] is set to option 2, 4, 5, 6, 13 or 14, and the digital input is active, A051
or A052 will override the speed reference commanded by this parameter. Refer to Chapter 1 of the PowerFlex 4 User
Manual for details.
P039 [Accel Time 1]
Sets the rate of accel for all speed increases.
P040 [Decel Time 1]
Sets the rate of decel for all speed decreases.
P041 [Reset To Defalts]
Resets all parameter values to factory defaults.
P043 [Motor OL Ret]
Enables/disables the Motor Overload Retention function.
Min/Max
Display/Options
0.0/[Maximum Freq]
0.1 Hz
0.0/[Maximum Freq]
0.1 Hz
0.00/(Drive Amps × 2)
0.01 Amps
0/Drive Rated Volts
1 VAC
Based on Drive Rating
1 VDC
0/1 (1 = Condition True)
Bit 3
Decelerating
F2/F122
F1
0.00/9999
0.01 – 1
0/9
Digit 1 = Speed Command
(See P038; 9 = "Jog Freq")
0/1 (1 = Input Present)
Bit 3
Reserved
0/1 (1 = Input Present)
Bit 3
Reserved
0/1 (1 = Condition True)
Bit 3
Fault Occurred
1.00/99.99
0.01
1001/9999
1
0/9999 Hrs
1 = 10 Hrs
0/FFFF
1 Hex
0.0/100.0%
0.1%
0.0/100.0%
0.1%
0/120 degC
1 degC
Min/Max
Display/Options
20/Drive Rated Volts
1 VAC
10/240 Hz
1 Hz
0.0/(Drive Rated Amps× 2) 0.1 Amps
0.0/240.0 Hz
0.1 Hz
0/240 Hz
1 Hz
0/5
0 = "Keypad"
1 = "3-Wire"
2 = "2-Wire"
0/7
0 = "Ramp, CF"
1 = "Coast, CF"
2 = "DC Brake, CF"
3 = "DCBrkAuto,CF"
0/5
0 = "Drive Pot"
1 = "InternalFreq"
2 = "0-10V Input"
0.0/600.0 Secs
0.1 Secs
0.1/600.0 Secs
0.1 Secs
0/1
0 = "Idle State"
1 = "Reset Defaults"
0/1
0 = "Disabled"
Bit 2
Bit 1
Accelerating
Forward
Digit 0 = Start Command
(See P036; 9 = "Jog")
Bit 2
Bit 1
Stop Input
Dir/Run REV
Bit 2
Bit 1
Reserved
Digital In2 Sel
Bit 2
Bit 1
RS485 Option Transmitting
(1)
3 = "2-W Lvl Sens"
4 = "2-W Hi Speed"
5 = "Comm Port"
(1)
4 = "Ramp"
(1)
5 = "Coast"
(1)
6 = "DC Brake"
(1)
7 = "DC BrakeAuto"
3 = "4-20mA Input"
4 = "Preset Freq"
5 = "Comm Port"
1 = "Enabled"
English-9
Bit 0
Running
Bit 0
Start/Run FWD
Bit 0
Digital In1 Sel
Bit 0
Receiving
Default
Based on Drive Rating
60 Hz
Based on Drive Rating
0.0 Hz
60 Hz
0
0
0
10.0 Secs
10.0 Secs
0
0

Publicité

Table des Matières
loading

Table des Matières