12 Technical Data
12 Technical Data
Connection to utility grid
Number of terminals
Rated grid input power
Rated operating voltage between L and N
Rated operating voltage between L1 and L2
Rated current / AC input current
Terminals for connection N, PE, L1, L2, L3
Minimum connectable conductor cross-section
Maximum connectable conductor cross-section
Fuse
Maximum permitted fuse rating for F330
Unaffected short-circuit current / relative rated short-circuit current at the terminals
Maximum permitted rated current of the back-up fuse
Short-circuit current breaking capacity of the back-up fuse
Forward current of the back-up fuse
Multicluster-Box connection
Number of terminals
Rated grid input power
Rated operating voltage between L and N
Rated operating voltage between L1 and L2
Rated current / AC input current
Terminals for connection N, PE, L1, L2, L3
Minimum connectable conductor cross-section
Maximum connectable conductor cross-section
Unaffected short-circuit current / relative rated short-circuit current at the terminals
Maximum permitted rated current of the back-up fuse
Short-circuit current breaking capacity of the back-up fuse
Forward current of the back-up fuse
Connection of grounding
Terminal for grounding conductor connection
32
GRID-BOX-12-3-20-BE-xx-12
SMA Solar Technology AG
1 x three-phase
138 kW
230 V
400 V
3 x 200 A
Spring-cage terminals
50 mm²
150 mm²
LV/HRC 1
200 A gG
≤17 kA
200 A gG
≥25 kA
≤17 kA
1 x three-phase
138 kW
230 V
400 V
3 x 200 A
Spring-cage terminals
50 mm²
150 mm²
≤17 kA
200 A gG
≥25 kA
≤17 kA
Spring-cage terminals
Operating manual