Maintenance; Disposal; Troubleshooting; Spare Parts - resideo Braukmann Triplex FF60 Instructions D'installation

Filtre à eau avec pré-filtre lavable, filtre fin et filtre à charbon actif
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

Maintenance

In order to comply with EN 806-5, water fixtures must
be inspected and serviced on an annual basis.
As all maintenance work must be carried out by an
installation company, it is recommended that a
servicing contract should be taken out.
If necessary, the outside surface of the filter can be cleaned.
Use only cold, clear drinking water to clean the surfaces.
Any other cleansers cause damage to the plastic
components!
In accordance with EN 806-5, the following measures must
be taken:
5.1 Inspection
Regular inspection of filter insert - approx. every 4
month.
• If contamination is high rinse preliminary filter 100
μm and replace fine filter 25 μm.
5.2 Maintenance
5.2.1 Filter bowl
1.
Close shut-off valve on inlet and outlet
2.
Release pressure on outlet side
3.
Unscrew filter bowl
4.
Remove filter cartridge
5.
Insert filter cartridge in new filter bowl
6.
Screw filter bowl in place
7.
Open shut-off valve on inlet
8.
Slowly open shut-off valve on outlet
7

Troubleshooting

Problem
Too little or no water pressure
8

Spare Parts

For Spare Parts visit homecomfort.resideo.com/europe
GB
5.2.2 Filter insert
1.
2.
3.
4.
5.
6.
7.
8.
6
Observe the local requirements regarding correct waste
recycling/disposal!
Cause
Shut-off valve on inlet is only opened
partially
Filter cartridge is contaminated
Filter is not fitted in flow direction
4
Replace the preliminary filter at least after 2 years or
after the third rinsing.
Replace the fine filter insert 25 μm if it is
contaminated, but at least after 6 month.
Replace activated carbon cartridge at least every 6
month.
Close shut-off valve on inlet and outlet
Release pressure on outlet side
Unscrew filter bowl
Remove filter insert
Clean or replace filter insert
• preliminary filter 100 μm can be rinsed with clear
water
• replace fine filter insert 25 μm if it is contaminated
• replace activated carbon cartridge if it is
contaminated
Screw filter bowl in place
Open shut-off valve on inlet
Slowly open shut-off valve on outlet

Disposal

Remedy
Open the shut-off valves fully
Replace filter cartridge
Fit filter in flow direction
MU1H-1150GE23 R0220