Omron E5AR-T Manuel D'instructions page 9

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 30
Control begins
Operation level
Program Setting Level
Confirm that Program
5. Set program
Editing is set to 1.
Set the number of
segments used with
the UD Key.
Set segment editing
with the UD Key.
Set the segment set
point with the UD Key.
Set the segment time
with the UD Key.
Adjustment Level
6. Change the
control period
Use the UD keys
to change the
control period
Alarm Set Setting Level
Confirm that the
7. Set alarm
Display Alarm Set
value 1
Selection is set to 1.
Use the UD keys
to set alarm value 1.
8. Start trial operation
RUN/RST
Adjustment Level
9. Execute AT
Use the UD keys
to execute AT
Operation Level
10. Begin operation
25.0
0.0
Present value / set point
01.01
Program No. Segment No.
Less than 1 second
prg.n
Program Editing
1
1:Program 1
01.00
M
s-no
Number of Segments Used
4
8→4:4
01.01
M
Program Editing
seg.n
end→1: Segment 1
1
01.01
M
sp
Segment
0.0
Set Point
01.01
M
time
Segment Time
0.00
01.01
M
Less than 1 second
spmd
SP mode
psp
off
l.adj
M
cp
Control period(Heat)
0.5
20.0→0.5:0.5 seconds
l.adj
Less than 1 second
d . alm
Display Alarm Set Selection
1
1:Alarm Set No.1
l.alm
M
1 . al-1
Alarm Set 1 Alarm Value 1
200.0
0.0→200.0: 200.0℃
l.alm
PF1
Press for at least 1 s to start operation (run).
Less than 1 second
at
AT execute / cancel
off
off → 0:AT execute
l.adj
Less than 1 second
25.0
Present value / set point
0.0
Program No. Segment No.
01.01
Begin operation
Make the settings
for segments 2, 3,
and 4 in the same
way.
* :means press
the key repeatedly
until the desired setting
l.adj
data appears.
l.alm
4. See auto tuning
(p. 9)
l.adj
*Perform autotuning
with the set point that
is the most important
for control.
During AT
execution
at
0
l.adj
After AT ends
at
off
l.adj
8

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

E5er-t

Table des Matières