Sets a short reversion after reaching the limit switch in open position. Can be useful for facilitat-
saso
ing the manual release.
Sets a short reversion after reaching the limit switch in close position. Can be useful for facilitat-
sasc
ing the manual release.
Selects the functioning mode of the auxiliary output 1 (N.O. clean contact)
0: Open barrier light, close contact when the barrier is open, open contact when the barrier is
close, intermittent during the maneuver (fig. 13, SCA)
1: Second radio cannel of the built in receiver
2: Boom light, for controlling the LED light installed on the BOOM (LADY.L), see also the pa-
aux1
rameter LBAR.
3: Courtesy light, the contact remains close according to the parameter TLS (fig.13 SERVICE
LIGHT)
4: Photocells test, see wiring diagram in Fig.13 (PHOTOTEST)
5: Close contact with open barrier
6: Close contact with close barrier
* ATTENTION: A WRONG SETTING OF THESE PARAMETERS CAN BE DANGEROUS.
RESPECT THE REGULATION IN FORCE!
MENU
Enables or disables automatic closing
TCA
On: automatic closing enabled
Off: automatic closing disabled
Enables or disables condominium function.
On: condominium function enabled. The step-by-step impulse or transmitter impulse has no
IbL
effect during the opening phase.
Off: condominium function disabled.
The multi-flat function is enabled or disabled during the TCA counting.
On: the bloc of flat function is enabled. The Step-by-Step signal or the transmitter signal has no
ibca
effect during the TCA counting.
Off: the bloc of flat function is disabled.
Enables or disables rapid closing
On: rapid closure is enabled. With open bar, or in the opening phase, the activation of the photocell
SCL
causes the automatic closure 3sec after the total opening of the gate. It is activated only with TCA:ON
Off: rapid closing disabled.
Selects the operating mode of the "Step by step button" and of the transmitter.
PP
On: Operation: OPEN > CLOSE > OPEN >
Off: Operation: OPEN > STOP > CLOSE > STOP >
Enables or disables pre-blinking.
PRE
On: Pre-blinking enabled. Blinking is activated 3s before the motor starts.
Off: Pre-blinking disabled.
Enabled or disables HOLD-TO-RUN function
On: HOLD-TO-RUN function.
htr
The pressure of the OPENS/CLOSES button must be maintained throughout the entire manoeuvre.
The opening of the STOP input stops the motor. All the safety inputs are deactivated.
Off: Automatic/semiautomatic function
Selects the operating mode of the blinking light during the time TCA
ltca
On: Blinking light on during TCA
Off: Blinking light off during TCA
Enables or disables checking of photocells on PHOT input, active both in closing and in opening.
On: Check enabled. If the check has a negative result, no manoeuvre is commanded. See Fig.13
TST1
- "PHOTO TEST".
Off: Checking of photocells disabled at each manoeuvre.
Enables or disables motors check.
TSTm
On: Check enabled. If the check has a negative result, no manoeuvre is commanded.
Off: Check disabled.
The code programmable transmitters is enabled or disabled.
On: Radio receiver enabled only for rolling-code transmitters.
Cvar
Off: Receiver enabled for rolling-code and programmable code transmitters (self-learning and
Dip Switch).
Selects the functioning mode of the boom light (24Vdc output on AUX2 or N.O. contact on the
output AUX 1 when configured at 2).
lBAR
On: The boom light is off when the barrier is close, it turns on when the barrier is in movement or open.
On: The boom light flashes slowly when the barrier is close (1s pause), it flashes quickly (0,5s
pause) when the barrier is in movement or open.
The "forced opening in case of power cut-off" function is activated or deactivated (it can be
activated only with connected and operating emergency batteries).
aopf
On: Activated function. In the event of power failure, the control unit causes an opening operation.
The barrier remains open until the power supply is back.
Off: Deactivated function.
14.3) LOGICS (LOG)
FUNZIONE
0-5 (0)
0-5 (0)
0-6-(0)
ON-OFF-(Default)
MEMO
(ON)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(OFF)
(ON)
(OFF)
(OFF)