5.2 Thermal overload protection

EDR 25, EDR 31, EDR 35, EDR 40
In the event of thermal overload, an
integrated motor overload protection switches
the fan off. After it has cooled off (up to 30
minutes) the unit automatically turns on.
EDR 45, EDR 50
Fan motor with thermal contacts (PTC
thermistors) connected to terminals. These
must be switched to a matching triggering
device, e.g., Maico motor protection switch
MVE 10 or the control circuit of a contactor.
The triggering device must not switch on
again automatically after being tripped.
EDR 56, EDR 63, EDR 71
Fan motor connected to thermal contact.
Engine monitoring with an optional frequency
converter.

6. Operation: Switching on/off

The fan is switched on or off with a switch
that is to be provided by the customer.
Ensure sufficient supply air during operation.

7. Technical data

For technical data,  the rating plate.
For dimensions and characteristic curves
 Internet (maico-ventilatoren.com).
Rated voltage
EDR 25, EDR 31,
EDR 35, EDR 40,
EDR 45, EDR 50
EDR 56, EDR 63,
EDR 71
Power frequency
Degree of protection
EDR 25, EDR 31,
EDR 35, EDR 40
EDR 63, EDR 71
EDR 45, EDR 50
EDR 56
230 V
400 V 3+N+PE
50 Hz
IP X4 when installed
in flexible ducts with at
least 1 m ducts on the
inlet and outlet sides
IP 54
5. Product information │ UK
Air volume
free outlet or
free inlet
Weight
EDR 25
EDR 31
EDR 35
EDR 40
EDR 45
EDR 50
EDR 56
EDR 63
EDR 71
Maximum airstream
temperature

8. Transport, storage

8.1 Transport
WARNING
Danger to life if impermissible means of
transport or lifting gear are used.
 Weight depending on type, see technical
data. Observe centre of gravity (middle).
 Observe the maximum permitted loading
capacity for lifting gear and means of
transport.
 Do not stand under a suspended load.
CAUTION
Risk of cuts from metal housing
plates with sharp edges.
 Wear protective gloves.
NOTICE
Risk of damage if means of transport are
incorrectly attached.
 Do not place load on sensitive
components, such as the impeller or
terminal box.
1700 to 20240 m³/h,
depending on unit
type
6.5 kg
14.9 kg
17.1 kg
12.8 kg
17.5 kg
22.8 kg
22.8 kg
39.3 kg
49 kg
45 °C to 80 °C,
depending on unit
type