Configuration - SOMFY animeo Notice D'installation

Masquer les pouces Voir aussi pour animeo:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

EN
A
PICTURES
[1]
IB+ 4 AC Motor Controller 2/3 EL WM 230 V AC,
wall mounted version
[2]
IB+ 4 AC Motor Controller 2/3 EL DRM 230 V AC,
DIN rail mounted version
B
MOUNTING
[1]
Choose the optimal location: flat and large surface
[2]
Mount the IB+ 4 AC Motor Controller 2/3 EL WM
or DRM
[3]
DIN Rail mounted version
1.
Electrical cabinet
[4]
Use cable tie!
[5]
Keep to minimum distance
C
WIRING
[1]
Tool for all terminals
[2]
Wiring diagram
[3]
Check the correct running direction of the
endpro ducts (group and local control inputs).
UP: end product moves upward (C +s)
STOP: end product stops (C +t+s)
DOWN: end product moves downward (C +t)
n To close window press UP,
to open window press DOWN
[4]
Possible switches
1.
Smoove Origin IB, Ref. 1811272
2.
Double push button unlocked
[5]
Local control
One local push-button can control motors on
several Motor Controller.
CABLE
Connection to ...
Motors
Switches
IB+ bus
230 V AC
Cables
Min.: 4 x 0.75 mm
/18 AWG
2
Max.: 4 x 2.5 mm
/13 AWG
2
Min.: 3 x 0.28 mm
/22 AWG
2
Max.: 3 x 2.5 mm
2
/13 AWG
Min.: 4 x 0.28 mm
/22 AWG
2
Max.: 4 x 1.5 mm
/15 AWG
2
Min.: 3 x 1.5 mm
/15 AWG
2
Max.: 3 x 2.5 mm
/13 AWG
2
D

CONFIGURATION

[1]
Reset / Prog button
With this button, you can access the basic
configuration of the Motor Controller.
[2]
Selection of switch ergonomic
Local push button ergonomics and the type of
end products to be preselected:
• Screen mode (SCR) - LED yellow
• Venetian blind, European mode - LED orange
(default mode)
• Venetian blind, US mode - LED red
• 3 end limit blind, European mode - LED yellow,
orange, red
1.
To toggle between modes, press shortly
the Reset / Prog button. Repeat until the LED,
according to the desired configuration,
lights up.
[3]
Factory RESET
[4]
Learn running and tilting times/length
1.
Press immediately when lower end limit
is reached
2.
Maintain stop for duration of tilting
3.
Release immediatly after complete turn
[5]
Learn and recall intermediate position (IP)
1.
Recording
2.
Recalling
[6]
Symbols: actions
1.
Up
2.
Stop
[7]
Symbols: end product status
1.
Up
2.
High position
3.
Down
4.
Low position
5.
Stop at the required position
6.
Short up and down movement
7.
Intermediate position (IP)
Twisted pairs
-
Recommended
Recommended
-
animeo IB+ 4 AC MOTOR CONTROLLER 2/3 EL . REF. 5125288C -
Max. distance
100 m/330 ft
1000 m/3,300 ft
6/12

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

18602441860245

Table des Matières