Contrôle des réglages - suite

EKA 164, EKA 166 ou AKM commande

Les fonctions du régulateur telles qu'elles apparaissent sur l'écran
EKA 164 et via le logiciel du système de type AKM sont présentées
dans les pages suivantes.
Pour accéder aux paramètres, appuyer sur le bouton du haut et le
maintenir enfoncé.
EKA-text
AKM text
Reference
r01
Neutral zone K
r04
Po sensor adjust
r12
Main switch
r13
Night offset K
r23
Po setpoint °C
r24
Comp. ctrl. Ref. °C
r25
Max reference °C
r26
Min Reference °C
r27
Night setback
r28
Pc setpoint °C
r29
Cond. ctrl. Ref. °C
r30
Min Reference °C
r31
Max Reference °C
r32
Pc sensor adjust
r33
Pc Reference mode
r35
Dimensioning tm K
r56
Min tm K
r57
Po °C
Capacity control
c08
Step mode
c10
+ Zone band K
c11
+ Zone delay s
c12
++ Zone delay s
c13
- Zone band K
c14
- Zone delay s
c15
-- Zone delay s
c16
Comp. application
c29
No. of fans
c31
Manual capacity %
c32
Cap. control mode
c33
Po pump down limit°C
c35
Load shed limit 1
AK-PC 710
R/W
Description / Parameter
W
Width of neutral zone for compressor control
W
Calibration of Po sensor
W
"Main switch for start/stop of control
ON: Normal control
OFF: Control is stopped"
W
Displacement value for suction pressure in con¬nection with an active
night setback signal (set in Kelvin)
W
Setting of required reference pressure in °C
R
Actual reference temp. for compressor capacity (incl. external reference
signal, if any)
W
Max. permissible suction pressure reference
W
Min. permissible suction pressure reference
R
Actual status of night setback
W
Setting of desired condensing pressure in °C
R
Reference for condenser in °C
W
Min. permitted condenser pressure reference
W
Max. permitted condenser pressure reference
W
Calibration of Pc sensor
W
"Choice of condenser pressure reference
0: Reference = Pc setpoint
1: The reference is changed as a function of Sc3 the external temperature
signal"
W
Dimensioning mean temperature differential between Sc3 air and Pc
condensing temperature at maximum load (compressor capacity = 100%).
Dimensioning temp difference at max load, typically 8-15 K).
W
Minimum mean temperature difference between Sc3 air and Pc condens-
ing temperature at no load (Compressor capacity = 0%)
R
Suction pressure in °C. (Measured with the Po pressure transmitter)
W
"Select coupling pattern for compressors
0: Sequential: Compressors are cut in/out in strict ac¬cordance with com-
pressor number (FILO)
2: Cyclic: Runtime equalisation between compressors (FIFO)
3: Best fit: Compressors are cut in/out in order to make the best possible fit
to actual load"
W
Width of "+ Zone" above neutral zone
W
Integrationtime in "+ Zone"
W
Integrationtime in "++ Zone"
W
Width of "- Zone" below neutral zone
W
Integrationtime in "- Zone"
W
Integrationtime in "-- Zone"
R
Readout compressor combinations
R
Read out number of fans
W
"Manual setting of compressor capacity
The value is in % of total capacity controlled by the controller"
W
Select whether capacity control is stopped, in manual control or controlled
via PI controller
W
Set the actual pump down limit for the last compressor
W
Set max compressor capacity limit for load shed input
Régulation de capacité RS8FT404 © Danfoss 03-2013
Range
Default
0,1 – 20,0 K
6,0 K
-10,0 - 10,0 Bar
0,0 bar
"ON: Normal control
OFF
OFF: Control is
stopped"
-25,0 - 25,0 K
0,0 K
-80,0 °C - 30,0 °C
-15,0 °C
-50,0 °C - 80,0 °C
80,0 °C
-80,0 °C - 25,0 °C
-80,0 °C
ON/OFF
-25,0 °C - 90,0 °C
35,0 °C
-25,0 °C - 100,0 °C
10,0 °C
-25,0 °C - 100,0 °C
50,0 °C
-10,0 - 10,0 Bar
0,0 bar
"0: Pc setpoint
1: Floating
1: Floating"
0,0 - 25,0 K
15,0 K
0,0 - 20,0 K
6,0 K
"0: Sequential
2: Cyclic
2: Cyclic
3: Best fit
"
0,1 – 20,0 K
4,0 K
10,0 – 900,0 s
300 s
10,0 – 900,0 s
300 s
0,1 – 20,0 K
3,0 K
10,0 – 900,0 s
150 s
1,0 – 300,0 s
30 s
0: Single step only
0: Single step
4: 1 x variable speed
only
+ single step
0 - 6
0
0 - 100%
0%
0: Manual control
2: Auto
1: OFF
2: Auto
-80,0 °C - 30,0 °C
-40,0 °C
0 - 100%
100%
67