INSTALLATION
BEFORE STARTING THE BURNER ALWAYS CHECK THE FOLLOWING:
- Burner and control unit have a proper earth connection.
- The on-burner nozzle (3) has a flow-rate suitable for the boiler.
- The nozzle holder (10) is fitted with the "O" marking facing upwards
- That there is fuel in the tank and the gates are open.
- The fuse on the electrical circuit is rated.
- The room and boiler thermostats are set to the desired temperature.
- The switch on any room thermostat is set.
- The main switch contacts are open.
- Any other control device has contacts closed.
- The air adjustment screw allows the throttle valve to open.
START-UP
- Reset by acting on the push-button.
- Power up by turning the main switch to ON. After the pre-ignition time has elapsed the
burner starts running and stays on until the temperature set on one of the control de-
vices causes the latter to trip (boiler thermostat, room thermostat etc.). During routine
operation the burner only shuts down when a control device is tripped.
- Adjust the flame by acting on both the air flow via the screw (13) and relative crown
(12) and on forward-rearward excursion of the nozzle holder (10). To adjust the latter
act on the screw (17).
- It is recommended that you bring the holder forward (+) for high or near-maximum
flow-rates and shift it back (-) for low flow-rates.
N.B. If the burner fails to start up check that the pump has been primed: if it has not,
act manually by undoing the gauge attachment screw and then screwing it back in as
soon as you notice fuel exiting the hole.
12
13
UK
40