Lamborghini Caloreclima ECO 8 Manuel D'installation Et D'entretien page 39

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GEARED MOTOR CONTROLLING AIR DELIVERY (ECO 15/2-ECO 20/2)
The geared motor limit switch and auxiliary contacts are triggered by easily accessible
adjustable cams, which can be set against o graduated scale.
SETTING THE CONTACT TRIGGERING POINT
General information:
CAM V (2 Stufe) - Cam controlling air valve fully open position (maz. firing rate with
both stages in operation).
CAM IV (1 Stufe) - Cam controlling minimum air flow condition (min. firing rate 1st stage
only in operation).
CAM II-III (MV1-MV2) - Auxiliari cam activating the 2nd stage valve.
RECOMMENDATIONS TO PROPERLY SET THE GEARED MOTOR
The geared motor is set upon testing as follows:
CAM V (2 Stufe) : is set on approx 90°-120°
CAM IV (1 Stufe) : is set on approx 25°÷50°.
CAM II-III (MV1-MV2): is set in such a way that the 2nd stage valve opens when the air
shut-off valve is at 60°÷80°.
Changes to this calibration during installation are legible even when the burner is in
operation by acting on the adjusting screws of the cams.
Tightening the screws increases the angle and positioning of the cams.
CAMMA II-III (MV1-MV2)
CAMMA IV (1 Stage)
CAMMA V (2 Stage)
Adjusting screws
UK
39

Publicité

Table des Matières
loading

Table des Matières