Télécharger Imprimer la page

Installation; General Information; Acoustic Emissions; General - Dimplex SIW 6TES Instructions D'installation Et D'utilisation

Publicité

Les langues disponibles

Les langues disponibles

English
6

Installation

6.1 General Information

The compact brine-to-water heat pump must be installed in a
frost-free, dry room on an even, smooth and horizontal surface.
The entire base of the frame should lie directly on the floor to
ensure an adequate soundproof seal. The surface must have
sufficient load bearing capacity for the weight of the heat pump
and the domestic hot water quantity. If supporting feet are
used, the heat pump must be installed horizontally. In this case,
the specified sound level can be up to 3 dB(A) higher, and addi-
tional sound insulation measures may be necessary.
The heat pump must be installed so that maintenance work can
be carried out without hindrance. This can be ensured by main-
taining a clearance of approx. 1 m in front of and, where neces-
sary, at the sides of the heat pump. If the heat pump is ac-
cessed from the front (e.g. installed in a recess etc.), the heat
pump module can be removed for after-sales service (see
Chapter 5).
1 (
m
)
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.

6.2 Acoustic Emissions

The heat pump operates silently due to efficient sound insula-
tion. Internal insulation measures should be carried out to pre-
vent vibrations from being transmitted to the foundation or to
the heating system.
7
Installation

7.1 General

The following connections need to be established on the heat
pump:
Flow and return of the brine (heat source system)
Flow and return of the heating system
Domestic hot water outlet
Cold water inlet
Voltage supply
Temperature sensor
EN-8

7.2 Connection on heating side

Flush the heating system prior to connecting the heat pump.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc. Any accumulation of deposits in the
liquefier may cause the heat pump to completely break down.
Once the heat pump has been connected to the heating sys-
tem, it must be filled, de-aerated and pressure-tested.
The maximum test pressure in the heating circuit and the
brine circuit is 4.0 bar.
This value must not be exceeded.
The following points must be observed when filling the system:
Scale formation in domestic hot water heating systems cannot
be avoided, but in systems with flow temperatures below 60 °C,
the problem can be disregarded. With high-temperature heat
pumps and in particular with bivalent systems in the higher per-
formance range (heat pump + boiler combination), flow tem-
1 (
m
)
peratures of 60 °C and more can be achieved. The following
standard values should therefore be adhered to with regard to
the filling and make-up water according to VDI 2035, sheet 1:
The total hardness values can be found in the table.
Total heat
output in kW
50 - 200
200 - 600
Fig. 7.1:Guideline values for filling and make-up water in accordance with
For systems with an above-average specific system volume of
50 l/kW, VDI 2035 recommends using fully demineralized
water and a pH stabiliser to minimize the risk of corrosion in the
heat pump and the heating system.
With fully demineralized water, it is important to ensure that
the minimum permissible pH value of 7.5 (minimum
permissible value for copper) is complied with. Failure to
comply with this value can result in the heat pump being
destroyed.
452236.66.09 · FD 9912
ATTENTION!
ATTENTION!
Untreated filling water and make-up water must be of
drinking water quality.
(colourless, clear, free of sediments)
Filling water and make-up water must be pre-filtered (max.
pore size 5 µm).
Total alkaline earths
in mol/m³ and/or
mmol/l
< 50
2,0
2,0
1,5
> 600
< 0,02
1. This value lies outside the permissible value for heat exchangers in heat
pumps.
VDI 2035
ATTENTION!
SIW 6TES - SIW 11TES
Specific system volume
(VDI 2035) in l/kW
20 < 50
50
< 20
Total hardness in °dH
16,8
11,2
 11,2
8,4
1
< 0,11
8,4
1
< 0,11
1
< 0,11
www.gdts.one

Publicité

loading

Ce manuel est également adapté pour:

Siw 8tesSiw 11tes