Troubleshooting the System continued...
Problem
Water on wrong days.
Incorrect display following
a power outage after being
plugged in.
"Current Time" is wrong
and flashing.
Display is flashing "FUS."
Display is flashing "SEN"
with no rainfall.
Valve will not turn off.
(Function switch Off
)
Display is flashing "OFF"
Blank display.
Possible Cause
Weekly or "SKIP DAYS"
schedule incorrectly set.
Current Day is wrong.
Battery is weak or missing.
Power outage occurred
with no battery or weak
battery in controller.
Excessive load.
Shorted solenoid or field
wires.
Rain Sensor operation.
Valve malfunction.
This is a reminder that the
function switch is in the
Off
position.
No power and discharged
battery.
Transformer unplugged.
2-Amp fuse blown.
Correction
See pages 13 & 14.
Set the correct date. See
page 13.
Remove AC power &
battery for one minute.
Replace battery, restore
power & repeat steps on
page 13.
Replace battery and reset
"Current Time."
Check maximum rating,
see page 8.
Check solenoids and
wiring, See page 20.
Check wiring and
connections on rain
sensor. If a rain sensor is
not connected, place the
sensor switch to BYPASS.
See page 3.
Check valve for leaks
and/or internal debris.
Use Dial to review settings
or switch to Run
to
begin watering.
Check circuit breaker
panel.
Plug in transformer.
Replace fuse.
See page 20.