Please note:
This function is not available in the USA and in Canada.
Installation tip:
When the buzzer on the UPS is switched on with the switch, an interrupted beam is indicated with a buzzer signal. This
function is very helpful after installation to check the proper function of the UPS as well as that of the connected light
curtain.
6.
Troubleshooting
Fault / Problem
Action
Door remains
Is the UPS (Universal Power Supply) power supply OK?
 Measure the main power on the connector. The main power must be 20 ... 265 VAC or
open; green and
orange LED on
 Check the power LED (green) on the UPS.
the edges are
Is any wire broken?
OFF
 Measure and check the main power cables.
 Measure and check the emitter and receiver cables by moving the cables by hand.
Door remains
Is the light curtain correctly connected to the UPS?
 Make sure that the emitter and receiver cables are connected to the UPS.
open; beams are
Is the grounding (PE) connection faulty?
not interrupted
 Make sure that the grounding (PE) is connected to the UPS.
Are the sensors looking "face-to-face"?
 It is important that the active parts of the emitter and receiver units are mounted so that they
Are the sensors or vision shields dirty?
 The active sensor part is the side with the black round lenses. Make sure that the black lenses
 Make sure that the vision shields are not painted or scratched.
Is any beam interrupted?
 Make sure that no object blocks the light path between emitter and receiver while the door is
Are the edges incorrectly aligned?
 The optical axis of the emitter (Tx) and the receiver edge (Rx) need to be aligned towards each
Is there excessive EMC interference e.g. from door drive?
 Do not guide the cegard/Mini-MOD connection cables close to cables carrying high voltage
Is there excessive light interference e.g. from fluorescent lamps?
 Do not install the cegard/Mini-MOD receiver edges directly exposed to light sources such as
Door closes only
Is the relay output logic set correctly?
 Check if the elevator / door controller needs a normally-open or normally-closed logic.
when an object
interrupts the
beams.
Random door
Is either the emitter or receiver cable damaged?
 Check for breaks in the cables by feeling the cables by hand.
openings
Is there any interference with the emitter from other infrared sensors (either directly or via
mirroring from shiny surfaces)?
 Avoid interference from blinking lights or infrared light sources such as photo cells or other
 Reflective surfaces near or parallel to the safeguarded area can cause reflections.
If a problem persists, please contact your local CEDES representative. Visit www.cedes.com for contact data.
8
20 ... 375 VDC.
face each other. The active sensor part is the side with the black round lenses.
are clean and not painted or scratched.
open and while the door is closing.
other to ensure the light curtain functions reliably.
and/or high current. The cegard/Mini-MOD cables should also be mounted as far away as
possible from the door drive motor or motor inverter (VVVF-drives) to avoid EMI problems.
FL tubes or energy saving lamps.
light curtains.
English
© CEDES | V 2.2