GUIDELINES FOR USING EXTENSION CORDS
that it is acceptable for outdoor use.
cord or have it repaired by a qualified person before using it.
Recommended Minimum Wire Gauge for Extension Cords (120 Volt)
Nameplate
Extension Cord Length
Amperes
25 Feet
(At Full Load)
0–2.0
18
2.1–3.4
18
3.5–5.0
18
5.1–7.0
18
7.1–12.0
18
12.1–16.0
14
16.1–20.0
12
ELECTRIC MOTOR LOADS
It is characteristic of common electric motors in normal operation to draw up to six times their running current while
starting. This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails
to start or reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the
requirements of the tool or appliance being used compared to the rated output of the generator.
MOTOR SIZE
RUNNING WATTS
1/8
1/6
1/4
1/3
1/2
3/4
1
1100
NOTE:
Operating voltage and frequency requirement of all electronic equipment should be checked before plugging
them into this generator. It may damage the equipment if the equipment is not designed to operate within a +/- 10%
voltage variation, and +/- 3 Herz frequency variation from the generator name plate ratings. To avoid damage, always
have an additional load plugged into the generator if solid state equipment (such as a television set) is used. A power
line conditioner is recommended for some solid state applications.
GENERATOR CAPACITY
Make sure the generator can supply enough continuous (running) and surge (starting) watts for the items you will
power at the same time. Follow the step below to prevent overload.
Add up the total rated wattage of all electrical items to be connected at one time. This total should NOT be greater
than generator's rated running wattage.
English

ELECTRICAL

50 Feet
75 Feet
18
18
18
18
18
16
16
14
14
12
12
10
10
8
WATTS REQUIRED TO START MOTOR
UNIVERSAL
275
N/A
275
600
400
800
450
950
600
1000
850
1200
N/A
7
100 Feet
150 Feet
18
16
16
14
14
12
12
12
10
8
10
8
8
6
CAPACITOR
SPLIT PHASE
850
1200
850
2050
1050
2400
1350
2700
1800
3600
2600
--
3300
--
200 Feet
16
14
12
10
8
6
6