BATTERY REPLACEMENT

Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the batteries:
Servicing the batteries should only be performed by professionals. For further information please contact your dealer.
Make a note for the replacement battery pack number, (RBP0027), regarding PR750ELCDRT1U and
PR1000ELCDRT1U models.
CAUTION! Use only the specified type of battery: HR9-6(BB) for PR750ELCDRT1U/ PR1000ELCDRT1U. Contact
your dealer for replacement batteries.
CAUTION! The battery may represent the risk of electrical shock. Do not dispose of batteries on fire, since they may
explode. Follow all local ordinances regarding the proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery can present a high risk for short-circuits and electrical shocks.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects from your hands.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of the battery or any battery terminals.
4. Wear rubber gloves and shoes.
5. Determine if the battery is grounded. If so, remove ground source. CAUTION: CONTACT WITH A GROUNDED
BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such a shock will be greatly reduced if such
grounding is removed during installation and maintenance.
BATTERY REPLACMENT PROCEDURE
Remove the front panel on the right
side.
Remove the retaining screw.
REMINDER! The used batteries are hazardous wastes and must be disposed through recycling. Most retailers that sell
lead-acid batteries collect used batteries for recycling, as required by the local regulations.
Remove the two retaining screws of
the cable protection cover, and then
remove the cover itself.
Put the new battery packs back into the compartment.
Tighten up the screws and replace the cable protection
cover and the front panel. Recharge the unit for at least 8
hours to ensure that the UPS performs to the expected
runtimes.
5
Disconnect the black and red wires
from the battery.