Table Des Matières; Safety Precautions; Installation Location - Mitsubishi Electric CITY MULTI PFFY-P20VKM-E Manuel D'installation

Masquer les pouces Voir aussi pour CITY MULTI PFFY-P20VKM-E:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 18
Contents
1. Safety precautions ................................................................................... 2
2. Installation location .................................................................................. 2
3. Installing the indoor unit ........................................................................... 3
4. Refrigerant pipe ....................................................................................... 4
5. Drainage piping work ............................................................................... 5

1. Safety precautions

s Before installing the unit, make sure you read all the "Safety precau-
tions".
s Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the "Safety Precautions," use,
and maintenance of the unit to the customer according to the information in the Op-
eration Manual and perform the test run to ensure normal operation. Both the Instal-
lation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
• Install the unit at a place that can withstand its weight.
• Use the specified cables for wiring.
• Use only accessories authorized by Mitsubishi Electric and ask the dealer or
an authorized technician to install them.
• Do not touch the heat exchanger fins.
• Install the air conditioner according to this Installation Manual.
Caution:
• Do not use the existing refrigerant piping, when use R410A or R407C refrig-
erant.
• Use ester oil, either oil or alkylbenzene (small amount) as the refrigerator oil
to coat flares and flange connections, when use R410A or R407C refrigerant.
• Do not use the air conditioner where food, pets, plants, precision instruments,
or artwork are kept.
• Do not use the air conditioner in special environments.

2. Installation location

B
Fig. 2-1
2
A
C
D
6. Embedding the indoor unit in a wall ......................................................... 6
7. Electrical work .......................................................................................... 7
8. Test run .................................................................................................... 8
9. Air outlet selection ................................................................................... 9
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts.
: Indicates that the main switch must be turned off before servicing.
: Beware of electric shock.
: Beware of hot surface.
: At servicing, please shut down the power supply for both the Indoor and
ELV
Outdoor Unit.
Warning:
Carefully read the labels affixed to the main unit.
• Have all electric work done by a licensed electrician according to local regu-
lations.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration from exceeding the safety limit even if
the refrigerant should leak.
• The cut face punched parts may cause injury by cut, etc. The installers are
requested to wear protective equipment such as gloves, etc.
• Ground the unit.
• Install an leak circuit breaker, as required.
• Use power line cables of sufficient current carrying capacity and rating.
• Use only a circuit breaker and fuse of the specified capacity.
• Do not touch the switches with wet fingers.
• Do not touch the refrigerant pipes during and immediately after operation.
• Do not operate the air conditioner with the panels and guards removed.
• Do not turn off the power immediately after stopping operation.
The indoor unit should be supplied with the following accessories.
(mm)
PARTNUMBER
1
Drain hose
2
Pipe cover
3
Band
4
Indoor unit mounting bracket
Fixing screw for 4 4 × 25 mm
5
6
Wood screw for the indoor unit fixation
Washer of 6
7
8
Felt tape (Used for left or left-rear piping)
9
MA Remote controller cable
2.1. Outline dimensions (Indoor unit) (Fig. 2-1)
The unit must be securely installed on a structure that can sustain its weight.
Models
A
P20/25/32/40
100 mm or more
Warning:
Mount the indoor unit on a wall structure strong enough to withstand the weight
of the unit.
ACCESSORY
B
C
100 mm or more
100 mm or more
QUANTITY
1
1
2
1
5
4
4
1
1
D
150 mm or below
from the floor

Publicité

Table des Matières
loading

Table des Matières