Parameter
Supply voltage
Nominal voltage
Nominal power
(base module only)
Mains fuse
Relay load
Permissible
cable type
The following components may be connected to one product
Controller modules D6
(6 x)
Controller modules D2
(2 x)
Total number of control circuits
Total number of thermal actuators Max. 72 *
Electrical safety
Protection class (EN 60730-1)
Degree of protection (EN 60529)
*) Note
AFRISO recommends the use of AFRISO actuators to ensure optimum sys-
tem performance. If actuators from other manufacturers are used, the fol-
lowing limit values must be met:
Operating voltage
Ma. operating current
Max. inrush current
Max. operating power
Special characteristic
Actuators of other manufac-
turers connected per control
circuit
Product description
Value
AC 230 V, 50 Hz to 60 Hz
1 VA
T 10 A
Max. 230 V, max. 2 A, power factor > 0.6
H03 VV-H2-F 2 x 0.75 mm²
Max. 3
Max. 9
Max. 18
II
IP 20
AC 230 V ±10 %, 50/60 Hz
9 mA
140 mA / 200 ms
Short-circuit proof, protected against
overvoltage
Max. 2
2 W
BM
EN
11