Object
Room temperature 1
Extract temperature 1
Exhaust temperature 1
Outdoor temperature 1
Supply temperature 1
Room humidity 1
Extract humidity 1
Exhaust humidity 1
Outdoor humidity 1
Supply humidity 1
CO 2 sensor bedroom (up to
8 rooms)
CO 2 sensor bedroom (set)
(up to 8 rooms)
CO 2 sensor room
(up to 8 rooms)
CO 2 sensor room (set)
(up to 8 rooms)
Humidity sensor bathroom
(up to 8 rooms)
Humidity sensor bathroom
(set)
(up to 8 rooms)
Error 1
Filter replace 1
Filter dirty 1
State
1 Refer to the manual of the ventilation unit for a description of this functionality.
2 When multiple types are indicated, the actual type can be configured by a parameter. See chapter 'Parameters'
Description
Reflects the room temperature sensor which is connected to the ventilation unit (if available)
Reflects the extract air sensor of the ventilation unit (SENSOR_ETA).
Reflects the exhaust air sensor of the ventilation unit. (SENSOR_EHA)
Reflects the outdoor air sensor of the ventilation unit.( SENSOR_ODA)
Reflects the supply air sensor of the ventilation unit. (SENSOR_SUP)
Reflects the room humidity sensor which is connected to the ventilation unit (if available)
Reflects the extract air sensor of the ventilation unit (HUMID_ETA).
Reflects the exhaust air sensor of the ventilation unit. (HUMID_EHA)
Reflects the outdoor air sensor of the ventilation unit.( HUMID_ODA)
Reflects the supply air sensor of the ventilation unit. (HUMID_SUP)
External CO 2 sensor input.
This object has to be connected to a KNX sensor that is mounted in a bedroom. Depending on
the measured CO 2 level, the ComfoConnect KNX C forces the ventilation unit to run at a minimum
ventilation preset.
� < 800 ppm: set to ventilation preset 1 at least;
� ≥ 800 ppm: set to ventilation preset 2 at least.
External CO 2 sensor input.
This object has to be connected to a KNX sensor that is mounted in another room other than a
bedroom. Depending on the measured CO 2 level, the ComfoConnect KNX C forces the ventilation
unit to run at a minimum ventilation preset.
� < 800 ppm: set to ventilation preset 1 at least;
� ≥ 800 and < 1200 ppm: set to ventilation preset 2 at least;
� ≥ 1200 ppm: set to ventilation preset 3 at least.
External humidity sensor input.
This object has to be connected to a KNX sensor that is mounted in a bathroom. Depending on the
measured humidity level, the ComfoConnect KNX C forces the ventilation unit to run at a minimum
ventilation preset.
� < 35%: set to ventilation preset 1 at least;
� ≥ 35%: set to ventilation preset 2 at least.
� False: all systems are operational;
� True: the ventilation unit reported an error. Manual inspection and/or intervention is required.
Check the error that is indicated on the display of the ventilation unit.
Hours till the ventilation units filter needs replacement.
� False: the ventilation units filters do not need replacing at this moment;
� True: the ventilation units filters need replacing.
State/error of the unit:
� 0: a connection with the ventilation unit has been established, no error;
� 30: another unit is detected; this unit is not connected to the ventilation unit;
� 40: incompatible ventilation unit version detected; cannot connect to the ventilation unit;
� 50: no ventilation unit detected.
For safety, when the state of the unit has any other value than 0, the Error object is set to True and
Standby is set to On.
Type 2
5.001
9.001
9.002
9.027
5.001
5.004
9.007
9.008
5.001
5.004
9.007
1.002
7.007
1.002
5.001
EN - 19