BMP 01-EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75
Magnetic Field Positioning System
7
IO-Link interface (continued)
7.4
System commands
Different commands are implemented in the BMP that can
be reached via parameter System Command on index 2,
subindex 0. Once a system command is transmitted to the
BMP, the command triggers the desired action, provided
that this action is permitted in the current application state.
Command Name
0x01 (1)
ParamUploadStart
0x02 (2)
ParamUploadEnd
0x03 (3)
ParamDownloadStart
0x04 (4)
ParamDownloadEnd
0x05 (5)
ParamDownloadStore
0x41 (65)
SP1 Single Value Teach
0x42 (66)
SP2 Single Value Teach
0x4E (78)
Teach Reset
0x80 (128)
Device Reset
0x82 (130)
Restore Factory Settings
0xA5 (165)
Reset Maintenance
0xE0 (224)
Teach Preset
0xE1 (225)
Teach Measurement
Range Lower Limit
0xE2 (226)
Teach Measurement
Range Upper Limit
Tab. 7-5:
System commands of index 2, subindex 0
20
english
Description
Starts parameter upload.
Ends parameter upload.
Starts parameter download.
Ends parameter download.
Completes the configuration and starts the data storage.
Saves the currently measured position as Setpoint 1.
Saves the currently measured position as Setpoint 2.
Deletes the SP1 and SP2 values of all SSCs.
Re-initializes all device components.
Resets all configurations to the factory setting.
Resets all operating parameters.
Calculates and saves the PDV offset, sets the current output value to the preset
value.
Teaches in the current position as a lower limit value of the measuring range.
Teaches in the current position as an upper limit value of the measuring range.