Warnings
...
,
Press ESC to hide an error message. It is displayed again after 10 seconds.
Press STOP to acknowledge an error message or a warning message. Remove the fault.
It is recommended to check the entered data.
Extended settings of control terminals
Multifunction input
X12.3
P452 1-voltage 0...10 V
X12.4
P562 2-current 0...20 mA
3-digital NPN (active: 0
V)
4-digital PNP (active: 24
V)
5-current 4...20 mA
6-voltage, characteristic
7-current, characteristic
6-: programmable characteristic via
P454...457
7-: programmable characteristic via
P564...567
Refer to operating instructions manual.
P: Parameter
Digital Input/ Output
X11.6
P558 0-input (default)
1-output
logic switchable digital inputs
X11.4 P559 0-NPN (active: 0 V)
X11.5
1-PNP (active: 24V)
X11.6
X12.1
X12.2
NPN: LOW-switching (on negative signal). Default of P562.
PNP: HIGH-switching (on positive signal). Default of P559.
Applications via control terminals
Enable
X11.3
X13.3
Change di-
X11.4
rection of
X11.5
rotation
Set motor
X12.3
speed
Agile
Quick Start Guide
Frequency inverter overloaded. Check load behaviour. Check motor parameters
and application parameters.
Overtemperature. Check cooling, fan and ambient temperature.
Max. motor temperature reached, check motor and sensor.
Mains phase failure, check mains fuses and supply cable.
Limit frequency reached, output frequency is limited.
Input signal at X12.3 is too low. Increase the value.
Input signal at X12.4 is too low. Increase the value.
DC link voltage has reached the type- specific minimum.
Digital signals at both terminals
Start clockwise by rising edge of the signal
Start anti clockwise by rising edge of the signal
Reference speed: DC 0 ... 10 V at analogue input. P452=1-voltage
(default). DC 0 V corresponds to 3.50 Hz (default value of P418).
DC 10 V corresponds to 50 Hz (default value of P419).
Multifunction output
X13.6 P550 1-digital MFO1D (P554*)
10-analogue PWM MFO1A (de-
fault) (P553*)
20-repetition frequency MFO1F
(P555*)
30-pulse train MFO1F (P557**)
Default:
1-: signal when output frequency exceeds 3 Hz (P510)
10-: output of voltage proportional to speed.
20-: frequency output 0...24 V proportional to speed
30-: output pulse train, scaled by P557.
* select a signal for the output.
** Scaling
X12.3 P452 3- digital input NPN (active: 0 V)
4- digital input PNP (active: 24 V)
X12.4 P562 3- digital input NPN (active: 0 V)
4- digital input PNP (active: 24 V)
44