Type
3~400 V
kW
F1
A
L1, L2, L3
mm
2
PE
mm
2
or
Type
3~230 V
kW
F1
A
L1, L2, L3
mm
2
PE
mm
2
or
Type
1~230 V
kW
F1
A
L1, N
mm
2
PE
mm
2
or
Connection on IT mains configuration
Agile
Quick Start Guide
-02...-11
-13
0.25...1.5
2.2
6
10
1.5
2 x 1.5
1 x 10
-01...-09
0.18...1.1
6
1.5
2 x 1.5
1 x 10
-01...-09
0.09...0.55
6
1.5
2 x 1.5
1 x 10
For connection on IT mains configuration remove the IT- jumper.
Note:
The removal of the IT jumper reduces the noise immunity. The
noise immunity can be improved by external filters.
-15
-18
-19
3.0
4.0
5.5
10
10
16
-11...-13
-15
1.5...2.2
3.0
10
16
-11...-13
-15
0.75...1.1
1.5
10
16
2.5
2 x 2.5
1 x 10
36
-21
-22
-23
7.5
9.2
11
25
25
35
2.5
2 x 2.5
2 x 4
1 x 10
1 x 10
-18
-19
4.0
5.5
25
35
2.5
4
2 x 2.5
2 x 4
1 x 10
1 x 10
-18
-19
2.2
3.0
25
35
4
2 x 4
1 x 10
05/2019
4
-21
7.5
35
6
2 x 6
1x10
-21
3.0
35