Télécharger Imprimer la page

turck TX-IO-DX06 Mode D'emploi page 3

Publicité

Les langues disponibles

Les langues disponibles

TX-IO-DX06
EN
Quick Start Guide
TX-IO-DX06 – Digital multifunction Plug-in I/O
Module
Properties
8 digital inputs
6 digital outputs
1 relay output
TX-IO-DX06 is a compact multifunction I/O module. It has been designed as an
optional plug-in for the HMIs of the TX500 product family.
TX-IO-DX06 provides typical industrial isolated digital inputs and outputs.
Specifications
Digital Inputs
Description
Specifications
Number of channels
8 digital inputs, 24 VDC, optoisolated
Input voltage range
12...30 VDC (min. 3 mA), 35 VDC max. for 500 ms
ON-state voltage/current
12...30 VDC (min. 3 mA)
6 mA @ 24 VDC, 9 mA @ 30 VDC
OFF-state voltage/current
max. 6 VDC, 1 mA
Input impedance
3,3 kΩ
Input filter delay
max. 50 μs
Debounce filter
Programmable 0.1 ms to 20 ms
Galvanic isolation
1500 Vrms
Digital outputs
Description
Specifications
Number of channels
6 digital outputs, 24 VDC, pnp, optoisolated
Output voltage
12...30 VDC
Output current
0.5 A per channel,
total current for all outputs max. 1.4 A
Output delay time
max. 150 µs
Output protection
Overcurrent and overtemperature protected
driver
Galvanic Isolation
1500 Vrms
Relay outputs
Description
Specifications
Number of channels
1, normally open
Load
Resistive
Rated load
1 A at 30 Vrms
Max. switching voltage
42.4 VAC (30 Vrms); 60 VDC
Max. switching current
1 A
Galvanic Isolation
1500 Vrms
Environmental Conditions
Description
Specifications
Operating
0...50 °C
Temperature
Storage Temperature
-20...70 °C
Operating Humidity
5...85 % relative humidity, non condensing
Protection class
IP20
Connection technology
Description
Specifications
Connector type
2 male connectors 10 pol., 3,5 mm grid/
Weidmueller - Omnimate BLZF 3.5/180F)
Dimensions
Voir fig. 1
Mounting
Remove the connector protective cover from the equipment before installing
the module and mount the module according to fig. 2.
Unmounting
ATTENTION
Risk of short circuits
Destruction of electronic circuits!
Do not connect or disconnect when energized.
Pin assignment/ connector view
Voir fig. 3
CN1 (Dig. Out.)
1
+ 24 VDC in
2
Relay
3
Relay
4
Out 1
5
Out 2
6
Out 3
7
Out 4
8
Out 5
9
Out 6
10
GND in
NOTE
The contacts 1 (+ 24 VDC in) and 10 (GND in) of the both connectors are inter-
nally connected.
Wiring Example
Voir fig. 4
NOTE
The maximum cable length is 30 m.
Approvals and standards
The product has been designed for use in combination with the HMIs of the
TX500 product family in an industrial environment in compliance with the
2014/30/EU directive.
Compliance
The products have been designed in compliance with:
EN 61000-6-4/ EN 61000-6-2
EN 61000-4-2 to -4-6, EN 61000-4-8
EN 55011, Class A
EN 60945
ATTENTION
Operation in
residential and commercial areas
Electromagnetic disturbances!
In case of the operation of the devices in residential and commercial areas,
observe the measurement values according to IEC-61000-6-3.
© Hans Turck GmbH & Co. KG | D301404 2016-06 DE EN FR
CN2 (Dig. Inp.)
1
+ 24 VDC in
2
In 1
3
In 2
4
In 3
5
In 4
6
In 5
7
In 6
8
In 7
9
In 8
10
GND in

Publicité