4.3.3 ADDING VENT SECTIONS

4.3.3 ADDING VENT SECTIONS
Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
least, 3 feet (1m) above its point of contact with the roof and at least 2 feet (0.6m) higher than any wall, roof,
least, 3 feet (1m) above its point of contact with the roof and at least 24 inches (61cm) higher than any wall,
building or obstacle within 10 feet (3m) horizontally.
EN
roof, building or obstacle within 10 feet (3m) horizontally.
EN
3 FT
3 FT
(1m)
(1m)
MIN
MIN

4.3.4 INSTALLING NATURAL VENT

4.3.4 INSTALLING NATURAL VENT
ADAPTER INSTALLATION:
ADAPTER INSTALLATION:
Remove the spill switch bracket from the rear of the
Remove the spill switch bracket from the rear of the adapter.
adapter.
Gently pull the two wire terminals (located inside the
Gently pull the two wire terminals (located inside the
7" (178mm) flue collar at the top of the appliance) out
7" (178mm) ue collar at the top of the appliance) out
approximately 8" (203mm).
approximately 8" (203mm).
Bring the wires through the lower hole in the adapter and out
Bring the wires through the lower hole in the adapter and
the spill switch opening. To pass the wires through the hole
out the spill switch opening. To pass the wires through
more easily, temporarily take the two terminals together.
the hole more easily, temporarily take the two terminals
With the spill switch opening aligned to the back of the
together.
appliance, take hold of the adaptor base and push the
With the spill switch opening aligned to the back of the
crimped edge into the appliance flue collar.
appliance, take hold of the adaptor base and push the
Connect the wire terminals to the spill switch and re secure
crimped edge into the appliance  ue collar.
the bracket.
Connect the wire terminals to the spill switch and re secure
the bracket.
For aesthetics, the adaptor has been designed to accept a standard
matte black 7" (178mm) appliance pipe and a decorative black band
For aesthetics, the adaptor has been designed to accept a standard
(standard with the GS150KT). Both are available from your local
matte black 7" (178mm) appliance pipe and a decorative black
authorized dealer / distributor.
band (standard with the GS150KT). Both are available from your local authorized dealer / distributor.
W415-1430 / 01.13.15
W415-1430 / B / 07.31.18
2 FT (0.6m) MIN
24" (61cm) MIN
10 FT (3m)
10 FT (3m)
TO NEAREST
TO NEAREST
ROOFLINE
ROOFLINE
10 FT (3m)
10 FT (3m)
OR MORE
OR MORE
FLAT ROOF
FLAT ROOF
REV B : Added metric dimensions
LESS THAN
LESS THAN
10 FEET
10 FEET
(3m)
(3m)
2 FT (0.6m)
24" (61cm)
RIDGE
RIDGE
MIN
MIN
3 FT (1m)
3 FT (1m)
3 FT (1m)
MIN
3 FT (1m)
MIN
MIN
MIN
3 FT (1m)
3 FT (1m)
MIN
MIN
LESS THAN
LESS THAN
10 FEET
10 FEET
(3m)
(3m)
24" (61cm)
2 FT (0.6m)
MIN
MIN
WALL
WALL
59.1B
ADAPTER
SPILL
SWITCH