4.2.5 APPLIANCE VENT CONNECTION

4.2.5 APPLIANCE VENT CONNECTION
A.
Attach the adjustable pipe to the last section of rigid pipe.
Secure with screws and seal.
B.
Install the inner  ex pipe to the appliance. Secure with
3 screws. Seal the joint and screw holes using the high
temperature sealant W573-0007 Mill-Pac (not supplied).
C.
Run a bead of high temperature sealant (not supplied) around
the inside of the air intake collar. Pull the adjustable pipe a
minimum 2" (50.8mm) into the air intake collar.
NOTE: Ensure that the sealant is not visible on the exterior pipes once installation is completed. An
optional decorative black band is available for this use. In the event that the venting must be disassembled,
care must be taken to reseal the venting.
#8 X 1/2"
SELF
DRILLING
2" (50.8mm)
SCREWS
OVERLAP
HIGH TEMPERATURE
SEALANT
W415-1430 / B / 07.31.18
W415-1430 / 01.13.15
23
23
EN
EN