G
®
KINASGARD
RBWF ⁄ LF
The room motion and light sensor KINASGARD
instrument that detects motions and light intensity as well as the presence of
persons and is used to recognize conditions. KINASGARD
standard signal of 0 - 10 V for light intensity and has a switching (changeover
contact) output for the detection of motions. This multisensor is used in build-
ing automation, in corridors, at workplaces, in industrial halls, in offices and
business facilities for the control of lighting as needed, e.g. to control sun-
shade equipment, for daylight-dependant constant light control, for activating
Venetian blinds or luminaries, for automatic energy conservation, and to avoid
unnecessary heating-up or cooling of unoccupied rooms.
TECHNICAL DATA:
Power supply: .............................. 24V AC ⁄ DC
Sensor: ......................................... infrared motion sensor and light sensor
Detection range: ........................ perimeter 360°, aperture angle 90° ⁄ 110°,
Motion detection: ....................... of persons and objects, necessary temperature
Output, motion sensor: ............. without ⁄ with motion,
After-running time: .................... adjustable from 4 s to 16 min
Measuring range, light sensor:... 0...1.000 Lux, other measuring ranges optional
Output, light sensor: .................. 0 - 10 V (linearised)
Measuring error: ........................ < ±10 % of final value
Ambient temperature: .............. 0 ...+ 50 °C
Electrical connection: ................ 0.14 - 1.5 mm²,
Enclosure: .................................... plastic, material ABS,
Dimensions: ................................. 85 x 91 x 27 mm (Frija I)
Installation: .................................. wall mounting or on in-wall flush box, Ø 55 mm,
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 30 (according to EN 60 529)
Standards: ................................... CE conformity, electromagnetic compatibility
NOTES
This device is used for the detection of persons in up to 10 meters distance.
The temperature difference between persons to be detected and ambience must be greater than 5 K.
When motion is detected, the potential-free relay output closes (-S) respectively opens (-Ö).
The hold time for the output (closed relay contact in case of -S, open relay contact in case of -Ö), measured from the time
when last motion was detected, can be pre-set at a potentiometer between 4 seconds and ca. 16 minutes.
The sensor is characterized by its broad reach while being small in size.
The potential-free normally-open ⁄ breaker contact is used for switching extra-low voltage only.
Type ⁄ WG1
1. Measuring Range
Detection
Presence ⁄ Motion
RBWF ⁄ LF
Yes ⁄ No
®
RBWF-LF is a combined
®
photodiode with glass case
reach ca. 10 m, circular
difference between subject and ambience ≥ 5 K
potential-free changeover contact 24 V
via terminal screws on circuit board
colour pure white (similar RAL 9010),
optional stainless steel
base with 4-hole for mounting on vertically or horizontally
installed in-wall flush boxes for cable entry from the back,
with predetermined breaking point for on-wall cable entry
from top ⁄ bottom in case of plain on-wall installation
according to EN 61 326 + A1 + A2, EMC directive 2004 ⁄ 108 ⁄ EC
2. Measuring Range
Light Intensity
0 ...1.000 Lux
Schematic diagram
RBWF-LF issues a
GND-terminals (1) and (3)
are connected on the circuit board.
Connecting diagram
1. Output
Presence ⁄ Motion
Changeover contact
Setting time interval
min. max.
4''
16'
1 2 3 4
5 6 7
1
UB- GND
2
UB+ supply voltage 24V AC/DC
3
GND
4
Output light 0-10V (linearised)
5
Normally open
contact
6
7
Breaker
2. Output
Light Intensity
0 -10 V
RBWF ⁄ LF
RBWF ⁄ LF