8.3
Technical data / Caractéristiques techniques / Datos técnicos
Weight
(lb)
(kg)
PDRD200
183
83
(*) Models for Canada with CRN, max working pressure is 174 PSIg (12 bar).
Electrical
supply inlet
PDRD200
230/1/60
Calibration values
PDRD200
Refrigerant
MIN.---MAX. Ambient temperature
Amb
R407C (kg)
R407C (kg)
During transport
and stockage
(oz)
(kg)
32 ---122˚F
45.8
1.3
0 ---50˚C
Compressor
1 M1
RLA
LRA
(A)
(A)
5.8
30
Hot gas valve
9
HGV
66.7 --- 69.6 PSIg
4.6 --- 4.8 barg
Compressed
air inlet
t
temperature
t
After
installation
In
41 ---122˚F
41 ---140˚F
5 ---50˚C
5 ---60˚C
Fan motor
3
EV1
RLA
(HP)
(HP)
(A)
0.53
0.19
Fan pressure switch
12 PV1
ON: 261 PSIg
OFF: 203 PSIg
ON: 18 bar
OFF: 14 bar
Connections
Air ---side
max. working
g
pressure
Compressed
air inlet/outlet
Max
203 PSIg (*)
1" 1/2 NPT---F
14 bar (*)
Minimum
Maximum
circuit ampacity
protection device rating
MCA
HACR
(A)
(A)
(A)
(A)
7.8
10
High pressure switch
15 HP1
406 PSIg
28 bar
Sound
p
pressure
l
level
l
Condensate
drain
[dB(A)]
1/2" NPT---F
55
Minimum section
validated cable for
validated cable for
eletrical connection
14AWG
High temperature thermostat
16 ST
248˚F
120˚C
19
PDRD200