The functions of each Dip Switch of the functional switch block are shown below:
SW1
SW2
OFF position
ON
SW3
SW4
OFF position
OFF position
OFF position
ON
ON
OFF position
ON
ON
SW5
SW6
OFF position
OFF position
OFF position
ON
ON
OFF position
ON
ON
SW7
OFF position
ON
Siren configuration
Learning procedure
Step 1:
Remove the screw from the bottom of the siren and remove the upper
cover.
Step 2:
Undo the two screws fixing the LED cover and remove the LED cover.
Step 3:
Set the control unit to learning mode; see the instruction manual of the
control unit for details.
Step 4:
Power the siren. All the LEDs will blink once and the buzzer will beep
once.
Step 5:
Press the Learn button once. The siren will beep once and the LED
groups 1 and 3 will light up for a short time. Now the siren is in learning
mode and will transmit to the control unit.
Step 6:
If the control unit has not received a learning code, press the learning
button again (the siren will not sound this time).
Step 7:
If the control unit receives the learning code, proceed on the control unit
as shown in its instruction manual. A confirmation message will be sent
to the siren. After having received the confirmation message, the siren
will beep once and the LED group 2 will blink once to indicate that the
learning process was successful. At that point, the siren will exit learning
mode.
<NOTE>
If the siren does not receive the confirmation code from the control unit within one minute, the siren will exit learning
mode and the LED groups 1 and 3 will be switched off.
Walk Test
Proceed with the Walk Test and installation after having concluded the learning operation.
Step 1: Deactivate the tamper function on the control unit. If the siren is installed on MP500/xx, access "Maintenance"
mode (see the instruction manual of the control unit for details). The siren will generate an acoustic signal to
indicate that the Tamper switch is off.
<NOTE>
The Tamper function will remain OFF for one hour. The control unit will return the function automatically back
to ON after this period of time.
Step 2:
Find the point where to install the siren.
Step 3:
Remove the upper cover by removing the screw on the bottom and carefully extracting the external container.
Step 4:
Remove the LED cover by loosening the two screws which fix it.
Step 5:
Check the radio connection level by setting the control unit in Walk Test mode and pressing the learn button.
Step 6:
If the test is successful, position the LED cover and fix it with two screws.
Installation
Step 1:
Identify the four mounting holes, install and fix the siren to the wall using the large screws and the anchor
bolts provided. Tighten the screws and make sure that the Tamper switch is fully pressed against the wall. If
there is a gap, fill it with suitable spacer material.
Reserved
Light alarm activation (LED groups 1-2-3)
Only during the acoustic alarm (default)
Until the system is deactivated
Alarm time
3 minutes (default)
5 minutes
10 minutes
1 second (sounded TEST use)
Volume control: siren sound, exit/entrance confirmation/delay sound
Reserved
Down
Medium
High (default)
Chime function (not managed on MP500/xx systems)
Off (default)
On
Upper cover
Lower screw