Toshiba RAV-SM2242DT-E Manuel D'installation page 40

Masquer les pouces Voir aussi pour RAV-SM2242DT-E:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Concealed Duct High Static Pressure
Error codes and parts to be checked
Wired remote
controller
display
Indication
No header remote controller
E01
Remote controller
communication error
Remote controller transmission
E02
error
Indoor unit-remote controller
E03
regular communication error
Indoor unit-outdoor unit serial
communication error
E04
IPDU-CDB communication error
E08
Duplicated indoor addresses
Duplicated header remote
E09
controllers
E10
CPU-CPU communication error
Header indoor unit-indoor
E18
follower unit regular
communication error
E31
IPDU communication error
Indoor unit heat exchanger
F01
sensor (TCJ) error
Indoor unit heat exchanger
F02
sensor (TC) error
Outdoor unit discharge temp.
F04
sensor (TD) error
Outdoor unit temp. sensor (TE/
F06
TS) error
F07
TL sensor error
Outdoor unit outside air temp.
F08
sensor error
Indoor unit room temp. sensor
F10
(TA) error
F12
TS (1) sensor error
F13
Heat sink sensor error
F15
Temp. sensor connection error
Indoor unit, other P.C. board
F29
error
F31
Outdoor unit P.C. board
Outdoor unit compressor
H01
breakdown
H02
Outdoor unit compressor lock
Outdoor unit current detect circuit
H03
error
H04
Case thermostat operation (1)
Outdoor unit low-pressure
H06
system error
Duplicated header indoor units
L03
Group line in individual indoor
L07
unit
L08
Indoor group address not set
L09
Indoor power level not set
L10
Outdoor unit P.C. board
39-EN
Main defective parts
Judging device
Remote
controller
Remote
controller
Indoor
Indoor
Indoor
Remote
controller
Indoor
Indoor
Outdoor
Indoor
Indoor
Outdoor
Outdoor
Outdoor
Outdoor
Indoor
Outdoor
Outdoor
Outdoor
Indoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Parts to be checked / error description
Incorrect remote controller setting --- The header remote controller has
not been set (including two remote controllers).
No signal can be received from the indoor unit.
System interconnecting wires, indoor P.C. board, remote controller
--- No signal can be sent to the indoor unit.
Remote controller, network adapter, indoor P.C. board --- No data is
received from the remote controller or network adapter.
System interconnecting wires, indoor P.C. board, outdoor P.C. board -
-- Serial communication error between indoor unit and outdoor unit
Indoor address setting error --- The same address as the self-address
was detected.
Remote controller address setting error --- Two remote controllers are
set as header in the double-remote controller control.
(* The header indoor unit stops raising alarm and follower indoor units
continue to operate.)
Indoor P.C. board --- Communication error between main MCU and
motor microcomputer MCU
Indoor P.C. board --- Regular communication is not possible between
header and follower indoor units or between twin header (main) and
follower (sub) units.
Communication error between IPDU and CDB
Heat exchanger sensor (TCJ), indoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger sensor (TCJ) was detected.
Heat exchanger sensor (TC), indoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger sensor (TC) was detected.
Outdoor temp. sensor (TD), outdoor P.C. board --- Open-circuit or
short-circuit of the discharge temp. sensor was detected.
Outdoor temp. sensors (TE/TS), outdoor P.C. board --- Open-circuit or
short-circuit of the heat exchanger temp. sensor was detected.
TL sensor may be displaced, disconnected or short-circuited.
Outdoor temp. sensor (TO), outdoor P.C. board --- Open-circuit or
short-circuit of the outdoor air temp. sensor was detected.
Room temp. sensor (TA), indoor P.C. board --- Open-circuit or short-
circuit of the room temp. sensor (TA) was detected.
TS (1) sensor may be displaced, disconnected or short-circuited.
Abnormal temperature was detected by the temp. sensor of the IGBT
heat sink.
Temp. sensor (TE/TS) may be connected incorrectly.
Indoor P.C. board --- EEPROM error
Outdoor P.C. board ---- In the case of EEPROM error.
Current detect circuit, power voltage --- Minimum frequency was
reached in the current releasing control or short-circuit current (Idc)
after direct excitation was detected
Compressor circuit --- Compressor lock was detected.
Current detect circuit, outdoor unit P.C. board --- Abnormal current was
detected in AC-CT or a phase loss was detected.
Malfunction of the case thermostat
Current, high-pressure switch circuit, outdoor P.C. board --- Ps
pressure sensor error was detected or low-pressure protective
operation was activated.
Indoor address setting error --- There are two or more header units in
the group.
Indoor address setting error --- There is at least one group-connected
indoor unit among individual indoor units.
Indoor address setting error --- Indoor address group has not been set. Entire stop
Indoor power level has not been set.
In the case of outdoor P.C. board jumper wire (for service) setting error Entire stop
– 39 –
Installation Manual
Air conditioner
status
*
*
Auto-reset
Auto-reset
Auto-reset
*
Auto-reset
Auto-reset
Entire stop
Auto-reset
Auto-reset
Entire stop
Entire stop
Entire stop
Operation
continued
Auto-reset
Entire stop
Entire stop
Entire stop
Auto-reset
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop