3.7

all terminations (propane) LV74

40'
38 ½'
(462")
35'
30'
V
20'
15'
10'
8 ½'
(102")
6'
(72")
4 7/8'
(58")
0'
Base of
1 ½'
air collar
(18")
2 ½'
(30")
0'
minimum venting requirements - propane
(PROPANE ONLY)
V+H ≤ 40 ft. H ≤ 4⅜ ft.
(For longer vent runs, a power vent is
required).
V + H are measured from the centre of vent
elbows. Elbows are considered as 90º.
Two 45º elbows = One 90º elbow.
For 0 elbow configurations, V is a minimum
of 6' to a maximum of 40'.
1-2 elbow zone
1 elbow zone
5'
10'
4 ⅜'
(52 ½")
3 ⅞'
(46 ½")
Vertical termination only.
No horizontal termination allowed.
Refer to appliance
specific GPV/PVA
instructions for other
venting configurations.
15'
H
25'
20'
W415-2034 / C / 04.21.21
EN
25