In spaces with combustion devices
Install the CO detector at 1 to 3 meters away from combustion devices, within the air flow
from the combustion device.
Install the CO detector way from of roof ridges, corners. arched ceilings or front roofs.
In the case of smaller spaces (<4m³), the detector should be installed outside these spaces.
Install the CO detector 60 centimeters from surrounding walls and ceilings.
Installation on both walls and ceiling is possible in rooms with a combustion device.