ERROR MESSAGES

GB
Problem
Diagnosis
The fan does not
Via the disconnecting switch
start up
Via the thermal magnetic circuit breaker
Screen is not lit (OFF)
Screen is lit (ON)
The fan unit starts
Screen is lit (ON)
then stops
The screen indicates an error during stoppage (Ex: E52)
The fan unit operates
The fan is operating under fire safety mode
at high speed without
any adjustment
The fan is operating,
The fan is certainly in the airflow reading mode
regulates, but does
not display the
pressure
Solutions
- Check the switch's electrical connections
- Check the input and output voltages on the switch.
- Check compatibility of I protection and I max. consumed.
- Check the internal power supply wiring.
- Change the PCB.
- Check that the number of the type of casing appears during
the first few seconds of switching on power. (e.g. 1,000 for
the iVEC 1000 micro-watt +), if this is not the case, contact
your nearest ALDES agency for reprogramming via the RS 232
computer interface.
- Check motor wiring.
- Change the motor. It is imperative that the cooling tube be
refitted around the motor.
- Check compatibility of I protection and I max. consumed.
- Check motor wiring.
- Resolve the anomaly by referring to the errors table.
- Check the state of the connection of the internal transparent
plastic tube
- Press the 'select' button to return to the desired mode.